Single enclosure unit
When using with the enclosure unit, design the semi-outdoor unit according to the following specifications to prevent
discharged hot air from flowing back into the inlet.
Air inlet( )
Total open area of the ventilation holes: 67,000 mm⁲ or more
Minimum ventilation opening ratio (%): 50 % or more
Air outlet( )
Total open area of the ventilation holes: 67,000 mm⁲ or more
Minimum ventilation opening ratio (%): 50 % or more
Design the locations of the enclosure unit inlet and outlet to match the locations of the semi-outdoor unit inlet and
outlet.
The front and back sides of the enclosure unit must be open without glass.
Keep clear around the product and the openings on the top and bottom to ensure good air flow.
Back Side view
Air inlet
Air outlet
English - 19