E-21
ENGLISH
Connecting the Unit (Continued)
Setup Simultaneous Control of Centralized Controller and the ERV Wired Remote Control
The ERV wired remote control is MASTER of COM2 communication, so it can communicate without
separate ADDRESS setting.
COM1 (F1, F2)
Transmitter 0
Centralized Controller
COM2 (F3, F4)
ERV Wired
Remote Control
Master Ventilator
MAIN:0
RMC:0
Ventilator
MAIN:1
RMC:0
Ventilator
MAIN:2
RMC:0
Ventilator
MAIN:3
RMC:0
Ventilator
MAIN:F
RMC:0
Level Setup of Centralized Controller
You can control the ventilator in multiple ways with DIP
switch
(DS01) setting on the centralized controller.
DIP Switch SW01 SW02 SW03 SW04 Remark
LEVEL 0 OFF OFF OFF OFF The ventilator operates with the last used control solution
LEVEL 1 ON OFF OFF OFF
When the centralized controller is OFF:
You can not use wired/wireless remote control.
When the centralized controller is ON:
You can use wired/wireless remote control.
LEVEL 2 OFF ON OFF OFF The ventilator operates only with the centralized controller.
LEVEL 3 ON ON OFF OFF
If the On/Off button is pressed once :
The operation indicator is turned on. The ventilator is on standby.
The ventilator operated with wired/wireless remote control.
If the On/Off button is pressed twice:
The operation indicator is turned off.
You can not operate the ventilator with wired/wireless remote control.
The centralized controller can be controlled by RMC ADDRESS of the ventilator, while the ERV wired remote
controller is controlled by COM2 communication.