EasyManua.ls Logo

Samsung RVMH050CBM0 - Page 11

Samsung RVMH050CBM0
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E-11
ENGLISH
Wiring Diagram of Connection Cord
Connection Cord Specifications
Indoor Unit 1
Outdoor Unit
Type A Outdoor unit
Indoor Unit 2 Indoor Unit 3
220V/60Hz
220-240V~/50Hz
208-230V~/60Hz
±10%
2.0mm
2
(HOS-RN-F,
2wires)
Ø1.6mm
(
HOS-RN-F
,
1wire)
0.75~
1.25mm
2
0.75~
1.25mm
2
Power Supply (Single Phase)
Earth Cable
Communication
Cable (HOS-
RN-F, 2wires)
Home server
(HOS-RN-F,
2wires)
Power Supply
Max/Min(V) Power Cable
When connecting cables, make the cable pass through the
cable tube as shown at the figure.
Must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and
communication cable.
CC
CC
AA
AA
UU
UU
TT
TT
II
II
OO
OO
NN
NN
Gas refrigerant pipe
Cable tube
Communication
cable
Connection cord
Power cable
Liquid refrigerant pipe
- Max. length of communication cable : 120m
- Whole length of cable : 240m
- Allowable branches : 10