5
ΙΛ
Model
Power supply
Remark
Performance
Power
Others
Size
Function /
Option
RVMH060GBM0 RVMH060GDM0 RVMH080GAM0
RVMH100GAM0
RVMH100GCM0
3, 380~415, 50
Set
55000(7000~55000)
16.0(2.0~16.0)
61000(7500~61000)
18.0(2.2~18)
57
57
ZRD72KC-TFD
Digital scroll
98.06
4.2
Propeller
128 x 2
95
8.0(5.0~8.0)
8.6(6.0~8.6)
5600(1800~5600)
5900(2800~5900)
2.9
R-22
8.0
EEV
Sontex 200LT
1890
9.52
22.20
-
150
166
930x1270x385
1124x1404x509
-5 to 43
-15 to 21
70
30
Set
55000(7000~55000)
16.0(2.0~16.0)
61000(7500~61000)
18.0(2.2~18)
57
57
ZRD72KCE-TFD
Digital scroll
98.06
4.2
Propeller
128 x 2
95
8.0(5.0~8.0)
8.6(6.0~8.6)
5600(1800~5600)
5600(2800~5600)
2.9
R407C
8.0
EEV
POE
1890
9.52
22.20
-
150
166
930x1270x385
1124x1404x509
-5 to 43
-15 to 21
70
30
Set
76000(7000~76000)
22.4(2~22.4)
85000(7500~85000)
25.0(2.2~25)
59
59
ZRDU13MC-TFD
Digital scroll +
Fixed scroll
98.04+82.59
4.2+3.5
Propeller
450
150
17.0
16.0
9500
9500
2.9
R-22
13
EEV
Sontex 200LT
1890 x 2
12.70
25.40
-
310
320
990x1765x780
1084x2090x984
-5 to 43
-15 to 21
100
50
Set
95500(7000~95500)
28.0(2.0~28.0)
107500(7500~107500)
31.5(2.2~31.5)
59
59
ZRDT14MC-TFD
Digital scroll +
Fixed scroll
162.40
4.2+4.2
Propeller
450
150
20 (5.8~20)
19 (6.5~19)
11000 (2300~11000)
10500 (2800~10500)
2.9
R-22
14
EEV
Sontex 200LT
1890 x 2
12.70
28.10
-
310
320
990x1765x780
1084x2090x984
-5 to 54
-15 to 21
100
50
Set
95500(7000~95500)
28.0(2.0~28.0)
107500(7500~107500)
31.5(2.2~31.5)
59
59
ZRDT14MCE-TFD
Digital scroll +
Fixed scroll
162.40
4.2+4.2
Propeller
450
150
20 (5.8~20)
19 (6.5~19)
11000 (2300~11000)
10500 (2800~10500)
2.9
R407C
14
EEV
POE
1890 x 2
12.70
28.10
-
310
320
990x1765x780
1084x2090x984
-5 to 43
-15 to 21
100
50
3, 380~415, 50 3, 380~415, 503, 380~415, 50
Heat pump
3, 380~415, 50
Btu/h
kW
Btu/h
kW
dB
dB
-
-
cc/Rev
kW
-
Watt
m
3
/min
A
A
Watt
Watt
Mpa
-
kg
-
-
cc
mm
mm
mm
kg
kg
mm
mm
°C
°C
m
m
ø, V, Hz
Capacity
Sound Level
(Front View)
✻
3)
Compressor
Fan output
Running current
Power input
Design pressure
Refrigerant
Refrigerant oil
Connecting pipe
Net weight
Shipping weight
Net dimension
(WxHxD)
Shipping dimension
(Carton/Case) (WxHxD)
Temperature
range (Outdoor)
Max. piping length
Max level difference
Cooling
✻
1)
Heating
✻
2)
Cooling
Heating
Model
Type
Piston displacement
Output
Type
Output
Air flow rate
Cooling
Heating
Cooling
Heating
Name
Charge
Control
Name
Charge
Liquid
Gas
Drain
Cooling
Heating
✻ 1) Indoor temperature : 27ºC DB, 19ºC WB / Outdoor temperature : 35ºC DB, 24ºC WB / Piping length : 10m, difference : 0m
✻ 2) Indoor temperature : 20ºC DB, 19ºC WB / Outdoor temperature : 7ºC DB, 6ºC WB / Piping length : 10m, difference : 0m
✻ 3) Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
DVM TM(chapter4-1)_E<03759 6/14/02 2:52 PM Page 5