EasyManua.ls Logo

Samsung RVMH050CBM0 - Wiring Diagram

Samsung RVMH050CBM0
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
. Installation
Λ
7. Wiring
32
ΛΛ
7-4. Wiring diagram
When using ELBs for 3 phase and 1 phase
When using ELB for 3 phase 4 wires
MCCB
ELB ELB
MCCB MCCB
Power Supply
Electrical component box
Case 1 Cut off the part A and B
Case 2
Indoor Unit
Communication
Cable
Single
Phase
3 Phase
3 Wires
Connection cord 3 Phase
Power Cable
Single
Phase
AC220V
Cable
clamp
Part A
Part B
Communication
Cable
Connection cord
3 Phase
Power Cable
Single
Phase
AC220V
Cable
clamp
MCCB
ELB
MCCB
Power Supply
Electrical component box
Indoor Unit
Communication
Cable
3 Phase
4 Wires
Connection cord 3 Phase
Power Cable
Cable
clamp
Power supply (1 phase)
Max/Min (V) Power cablePower supply
Communication cable
(VCTF, 2wires)
Earth wire
Home server
(VCTF, 2wires)
220V / 60Hz
220-240V/50Hz
208-230V/60Hz
± 10% 0.75~1.25mm
2
0.75~1.25mm
2
1.6mm
(IV, 1wire)
2.0mm
2
(CV, 2wires)
The power supply cable shall be connected to the power supply terminal and shall be fixed with clamp as in the following figure.
The unbalance of power shall be within 2% of power supply rating.
- If the power supply unbalance is great, the lifetime of condenser is shortened.
- If the power supply unbalance exceeds 4%, the indoor unit stops and error mode displays.
7-3. Connection cord specification
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 32