3. Functional parts and safety devices
12
. Outdoor unit
ΙΛ
ΙΛ
ΙΛ
Item Code Name
RVMH100GCM0
Motor output
Compressor safety OLP
Crank case heater
Fan motor
Safety thermostat
High pressure switch
Low pressure switch
High pressure sensor
Low pressure sensor
Thermistor (discharge)
Thermistor (condenser center)
Thermistor (condenser outlet)
Thermistor (outdoor temperature)
Suction sensor
Oil sensor
Thermistor (fixed discharge)
Solenoid valve
(for compressor operation)
Solenoid valve
(for bypass of high temperature gas)
Solenoid valve (liquid injection)
Solenoid valve (for exhaust air)
Solenoid valve (for capacity control)
Solenoid valve (for capacity control)
4-way valve
Check valve
Electronic expansion valve (for heating)
90W
OSME4506SRC
450W
150°C
100°C
ZRDT14MCE-TFD
4.2kW + 4.2kW
155
°C
70A
OFF : 33(±1)kg/cm
2
ON : 24(±1)kg/cm
2
PS8030A (NH4-H)
(0~30kg/cm
2
)
(TOYOTA)
PS8030A (NH4-L)
(0~10kg/cm
2
)
(TOYOTA)
Model : 0166-01, Rt=150°C, 25°C=86Ω
-
103AT (25°C=10kΩ)
103AT (25°C=10kΩ)
103AT (25°C=10kΩ)
103AT (25°C=10kΩ)
204CTB (25°C=200kΩ)
Coil : Copeland (Part # 023-0028-03)
Body : EPV-1530D
Coil : Siginomiya
Body : NEV-603D
Coil : Siginomiya
Body : NEV-202D
-
-
Coil & Body : CHV-0712 (Saginomiya)
Fujikoki (30kg/cm
2
)
EDM-AOYP (Fujikoki)
-
-
-
CCH
Motor
HPS
LPS
HPSO
LPSO
DTS
CMS
COS
OATS
SUC.S
OIL.S
FDTS
PWM
HGBV
LBV
VBV
BV1
BV2
4-W/V
C/V
EEV
Compressor
Safety
devices
Temperature
sensor
Functional
parts
open temp.
trip current
model
output
on
off
DVM TM(chapter4-1)_E<03759 6/14/02 2:52 PM Page 12