4) VIEW mode
According to the number of pushes on KEY 4, displays the proper data, and if the model contains no
content to display, display only the number of pushes on SEG 1.
4-1 Input 1 time: Displays the data of high pressure (displays down to three decimal places)
Ex.) In the case of the high pressure is 21.2kg/cm
2
SEG 1: 1 flickers SEG 2, 3, 4: each of them, displays 2, 1, 2
4-2 Input 2 times: Displays the data of low pressure (displays down to one decimal places)
Ex.) In the case of the low pressure is 8.2kg/cm
2
SEG 1: 2 flickers SEG 2, 3, 4: each of them (None), displays 8, 2
4-3 Input 3 times: Displays the discharge temperature of PWM compressor (Internal PWM sensor)
Ex.) When the discharge temperature of compressor is 101°C
SEG 1: 3 flickered SEG 2, 3, 4: each of them, displays 1, 0, 1
4-4 Input 4 times: display the condensation temperature
Ex.) When the condensation temperature is 101°C
SEG 1: 4 flickered SEG 2, 3, 4: each of them, displays 1, 0, 1
4-5 Input 5 times: Displays outdoor temperature
Ex.) When the temperature is 30°C
SEG 1: 5 flickered SEG 2, 3, 4: each of them (None), displays 3, 0
4-6 Input 6 times: Displays the STEP of electronic expansion valve
(shows the STEP/10, and the rest would be omitted)
Ex.) When the STEP of electronic expansion valve is 1002
SEG 1: 6 flickered SEG 2, 3, 4: each of them, displays 1, 0, 0
4-7 Input 7 times: Displays the temperature of COND OUT
Ex.) When the discharge temperature of condenser is -10
SEG 1: 7 flickers SEG 2, 3, 4: each of them, displays -, 1, 0
4-8 Input 8 times: Displays the temperature of oil
Ex.) When the temperature of oil is 22°C
SEG 1: 8 flickers SEG 2, 3, 4: each of them(None), displays, 2, 2
4-9 Input 9 times: Displays the temperature of SUCTION
Ex.) When the temperature of SUCTION is 22°C
SEG 1: 9 flickers SEG 2, 3, 4: each of them(None), displays 2, 2
4-10 Input 10 times: Displays STEP of outdoor fan
Ex.1) When the STEP of outdoor fan is 12 in SSR fan controlling(20 step)
SEG 1: A flickers SEG 2, 3, 4: each of them(None), displays 1, 2
Ex.2) When the STEP of outdoor fan is 4 in RELAY fan controlling(5 step)
SEG 1: A flickers SEG 2, 3, 4: each of them(None), displays 0, 4
4-11 Input 11 times: B flickers in SEG 1
4-12 Input 12 times: Stops VIEW mode, and display the communication data
SEG 1, 2: Display the communication data
SEG 3, 4: Display the STEP of outdoor fan (total 20 step)