Troubleshooting
26 Samsung Electronics
6-3-15 (P) Check no gas error
Charge standard amount of refrigerant.
6-3-16 (Q) Check of 4-Way valve
Check whether the wires of 4-Way valve and control board of outdoor units correct.
If it is normal, replace 4-Way valve.
6-3-17 (R) Check of outdoor unit fan motor (SH12BPHX only)
Check whether the wire of fan motor is connected to the control board (CN01) of outdoor unit.
Check the voltage on the control board of outdoor unit and if it is same as follows, replace fan motor.
Input power AC178V~AC264V.
CN01 1-3pin : DC250V±10% ~ DC370V±10%
CN01 4-3pin : DC15V
DB98_19047A(1)_1 4/21/04 2:27 PM Page 27