SAMSUNG | 49
FEATURES & OPERATION
6
Details for Operation Property (Cont.)
6-2-7. Overload protection control
AT HEATING MODE
If indoor heat exchanger temp. is over 53°C, outdoor fan turns off.
If indoor heat exchanger temp. is over 60°C, outdoor compressor stops and Indoor fan speed is low.
After compressor and fan are off if indoor heat exchanger temp. is below 50°C, indoor fan and outdoor compressor and outdoor
fan operate normally.
Indoor Heat Exchanger Temp.
60˚C + offset
53˚C + offset
50˚C + offset
Compressor
Outdoor Fan
Indoor Fan
On
On
Time
On
Off
Off
Low Speed
3min Delay
2Sec
On
Setting Speed
*offset = 0, 1, 2, 3˚C