EasyManua.ls Logo

Samsung SINGLE AC N Series - Page 63

Samsung SINGLE AC N Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
365
Installation
In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Main power terminal block specifications
1-phase terminal block specifications
AC100/120/140RXADKG
1(L) 2(N)
F1 F2
L N
16.3 12 11.4
10.1
3-phase terminal block specifications
AC100/120/140RXADNG
1(L) 2(N) L1(R) L2(S) L3(T) N
9.8 14.2 11.4
F1 F2
10.1
Main power cable specifications
The power cable is not supplied with air conditioner.
Select the power supply cable in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single phase
Model Outdoor unit Input current (A) Power supply
Indoor unit Outdoor unit Hz
Voltage range (V) Outdoor unit
Indoor
unit
Total MCA (A) MFA (A)
Rated Min. Max. Cooling Heating
AC100RN4DKG
AC100RXADKG
50 220 to 240 198 264
24.0 24.0
1.0 25.0 25.0 30.0
AC100RN4PKG 1.5 25.5 25.5 30.0
AC100RNMDKG 2.5 26.5 26.5 30.0
AC100RNCDKG 2.5 26.5 26.5 30.0
AC100RNTDKG 1.6 25.6 25.6 30.0
AC120RN4DKG
AC120RXADKG
1.0 25.0 25.0 30.0
AC120RN4PKG 1.5 25.5 25.5 30.0
AC120RNMDKG 2.5 26.5 26.5 30.0
AC120RNCDKG 2.5 26.5 26.5 30.0
AC140RN4DKG
AC140RXADKG 32.0 32.0
1.0 33.0 33.0 40.0
AC140RN4PKG 1.5 33.5 33.5 40.0
AC140RNMDKG 2.5 34.5 34.5 40.0
AC140RNCDKG 2.5 34.5 34.5 40.0

Related product manuals