SAMWONTECH
1st Edition of TEMI2000_Series IM : Dec. 15. 2008 Page 42 / 58
7.16 PROGRAM PATTERN Group and Setting
7.16.1 PROGRAM Group
PROGRAM group consists of parameter D-Register to arrange program PATTERN organized by each segment profile.
Each segment should be established step by step.
█ Program PATTERN setting D-Register
D-Reg. Symbol Range Description
D1701 COM_PTNO 1~120 Program PATTERN number to Read or Write
0 To Read or Write in D1736~D1757
D1702 COM_SEGNO
1~99 Segment number to Read or Write
D1703 PTCOPY_START - First target (START) pattern number to paste
D1704 PTCOPY_END - Last target (END) pattern number to paste
D1705 PTDEL_START - First target (START) pattern number to delete
D1706 PTDEL_END - Last target (END) pattern number to delete
1 INIT : Initialize D1701~D1708 to '0'
2 READ : Read profiles in D1701 and D1702
3 WRITE : Write profiles in D1701 and D1702
4 PT COPY : Copy PTN in D1701 to PTN designated in D1703~1704
5 PT DEL : Delete PTN designated in D1705~D1706
6 PT NAME READ : Read PTN NAME in D1701
7 PT NAME WRITE : Write PTN NAME in D1701
D1707 TRIGGER
8 ALL PT : Write pattern profile at D1701 into D2100
0 FULL : Excessive number of pattern or segment setting
1 DONE : Normally accessed of D1707(TRIGGER) command
2 PT EMPTY : No profile in designated pattern
3 SEG EMPTY : No profile in designated segment
4 PT RUN : Program RUN state of designated PTN
D1708 ANSWER
5 PARA ERROR : Program setting Error of D1701~D1707
D1711~D1722 PATTERN_NAME1~12 - Pattern NAME to Read or Write
D1725 TEMP.TSP - TEMP. Target Set Point(TSP) to Read or Write
D1726 HUMI.TSP - HUMI. Target Set Point(TSP) to Read or Write
D1727 SEG.TIME_H - Target Process time (HOUR) of segment to Read or Write
D1728 SEG.TIME_L - Target Process time (MIN & SEC) of segment to Read or Write
D1729 TS1 - TS1 to Read or Write
D1730 TS2 - TS2 to Read or Write
D1731 TS3 - TS3 to Read or Write
D1732 TS4 - TS4 to Read or Write
D1733 SEG.WAIT - WAIT to Read or Write