5.3 ERROR Response
When an Error occurs during communication, TEMP2500 transmits a frame as following.
bytes 1 2 2 2 2 1 1
Frame STX Address NG Error Code SUM CR LF
Description of Error Code
Error Code Description Remarks
01 Invalid Command setting
02 Invalid D-Register setting
04 Data Setting Error
Invalid text data input
(Available 0~9, A~F : hexadecimals)
08 Invalid Format configuration
▪ Different command format with designated
▪ Differnet number of setting with designated
11 CheckSum Error
12 Monitoring Command Error No setup Monitoring Command
00 Other Errors