SAMWONTECH
1th Edition of TEMP2000_Series IM : Dec. 15. 2008 Page 43 / 63
7.17 PROGRAM PATTERN Group and Setting
7.17.1 PROGRAM
PROGRAM group consists of parameter D-Register to arrange program PATTERN organized by each segment profile.
Each segment should be established step by step.
Program PATTERN setting D-Register
D-Reg. Symbol Range Description
D2101 COM_PTNO 1~80 Program PATTERN number to Read or Write
0 To Read or Write in D2145~D2167
D2102 COM_SEGNO
1~99 Segment number to Read or Write
D2103 PTCOPY_START - First target (START) pattern number to paste
D2104 PTCOPY_END - Last target (END) pattern number to paste
D2105 PTDEL_START - First target (START) pattern number to delete
D2106 PTDEL_END - Last target (END) pattern number to delete
1 INIT : Initialize D2101~D2108 to '0'
2 READ : Read profiles in D2101 and D2102
3 WRITE : Write profiles in D2101 and D2102
4 PT COPY : Copy PTN in D2101 to PTN designated in D2103~2104
5 PT DEL : Delete PTN designated in D2105~D2106
6 PT NAME READ : Read PTN NAME in D2101
7 PT NAME WRITE : Write PTN NAME in D2101
D2107 TRIGGER
8 ALL PT : Write pattern profile at D2101 into D2300
0 FULL : Excessive number of pattern or segment setting
1 DONE : Normally accessed of D2107(TRIGGER) command
2 PT EMPTY : No profile in designated pattern
3 SEG EMPTY : No profile in designated segment
4 PT RUN : Program RUN state of designated PTN
D2108 ANSWER
5 PARA ERROR : Program setting Error of D2101~D2107
D2111~D2122 PATTERN_NAME1~12 - Pattern NAME to Read or Write
D2126 TSP - Target Set Point(TSP) to Read or Write
D2127 SEG.TIME_H - Target Process time (HOUR) of segment to Read or Write
D2128 SEG.TIME_L - Target Process time (MIN & SEC) of segment to Read or Write
D2129 TS1 - TS1 to Read or Write
D2130 TS2 - TS2 to Read or Write
D2131 TS3 - TS3 to Read or Write
D2132 TS4 - TS4 to Read or Write
D2133 TS5 - TS5 to Read or Write
D2134 TS6 - TS6 to Read or Write
D2135 TS7 - TS7 to Read or Write
D2136 TS8/AUX_OUT - TS8 or AUX to Read or Write
D2137 SEGAL1 - SEGMENT ALARM1 to Read or Write
D2138 SEGAL2 - SEGMENT ALARM2 to Read or Write
D2139 SEGAL3 - SEGMENT ALARM3 to Read or Write
D2140 SEGAL4 - SEGMENT ALARM4 to Read or Write
D2141 SEG_PID - SEGMENT PID to Read or Write