14 S&C Instruction Sheet 695-545
STEP 6. Repair the fault in accordance with your
company’s operating procedures and rules.
STEP 7. When you are ready to re-energize the circuit,
rotate the manual operating handle clockwise to
close the fault interrupter. See Figure 18.
STEP 8. Check the POSITION indicators to con rm the
fault interrupter is closed. See Figure19.
STEP 9. Con rm the position of the isolating disconnect
using the large viewing window. See Figure 20.
STEP 10. Return the manual operating handle to its
storage location.
Figure 18. Closing the fault interrupter.
Figure 19. The POSITION indicator after the fault interrupter
has been closed.
Figure 20. The isolating disconnect after the fault interrupter
has been closed.