1.5. Performance
The MD range of Dehumidifiers has been designed to operate between the following conditions:
This corresponds to an approximate minimum wet bulb temperature of 13 C and maximum of 31 C.
Performance is dependant upon both dry bulb temperature and relative humidity as shown in figure
6.
The moisture removal for a range of operating conditions is shown in the curves below:
oo
100 unit
0
50
100
150
200
20 25 30 35 40 45
Temperature (°C)
litres/day
40%RH
60%RH
80%RH
160 unit
0
50
100
150
200
250
300
20 25 30 35 40 45
Temperature (°C)
litres/day
80%RH
60%RH
40%RH
200 unit
0
50
100
150
200
250
300
350
20 25 30 35 40 45
Temperature (°C)
litres/day
40%RH
80%RH
60%RH
Figure 6. Dehumidification rates for a range of operating conditions
Page 7
Lower Limit
Upper Limit
Dry Bulb Temperature
(C)
o
Relative Humidity (%)
40
50
40
21
QA/IOM/46 Issue 11 - MD Dehumidifier