EasyManua.ls Logo

Sanyo 12KHS32 User Manual

Sanyo 12KHS32
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
SUBMITTAL SHEET
SYSTEM
INDOOR/OUTDOOR
12KHS32
KHS1232/CH1232
WALL MOUNTED HEAT PUMP
GENERAL DATA (AT 230V)
POWER V/PH/HZ 230-208/1/60
Circuit Ampacity, Min. (A) 20
Fuse size, Max. (A) 20
COMPRESSOR Rotary-Hermetic
No. used 1
R.L. Amps - L.R. Amps (A) 5.5 - 34
Crankcase Heater 20W
OUTDOOR FAN - TYPE Propeller
Dia. (in.) - No. used 15-3/4 - 1
Type Drive - No. speeds Direct - 1
No. Poles – RPM 6 - 840
No. Motors – HP 1 - 1/38
CFM (High) 820
F.L. Amps. (A) 0.4
OUTDOOR COIL – TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Corrugated Plate - Inner Riffled
Rows - F.P.I. 2 - 15.9
Face Area (sq.ft.) 3.29
Tube Size (in.) 3/8
INDOOR FAN – TYPE Cross - Flow
Dia. & Length (in.) - No. used 4 & 30 - 1
No. speeds 3 & Auto
No. Poles -RPM (High) 4 -1,330
No. Motors - HP 1 - 1/75
CFM (HI/MED/LOW) 360/310/260
F.L. Amps (A) 0.2
INDOOR COIL - TYPE Aluminum Fin & Copper Pipe
Fin Type - Pipe type Slit Plate - Inner Riffled
Rows - F.P.I. 2 - 14.1
Face Area (sq. ft.) 2.08
Tube Size (in.) 3/8
Drain Connection Size (in.) 1 - 1/4
REFRIGERANT R22
Lbs. - R22 (O.D. Unit) 2.51
Control Capillary Tube
Connection Flare
Line Length, Max (ft.) 65
Lift difference, Max (ft.) 23
Line Size - in. O.D. Discharge 1/4
Line Size - in. O.D. Suction 1/2
DIMENSIONS (in.) H x W x D
Indoor Unit -Uncrated 14-3/16 x 39 x 7-13/16
-Crated 18-1/32 x 42-17/32 x 10-23/32
Outdoor Unit -Uncrated 20- 7/8 x 29-17/32 x 11-1/32
-Crated 23-17/32 x 35-13/32 x 13-7/8
WEIGHT INDOOR OUTDOOR
Net (lbs.) 29.8 92.6
Shipping (lbs.) 37.5 99.2
Shipping Volume(cu.ft.) 4.8 6.7
SS12KHS32-1
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
COOLING
Total Capacity (BTU/H) 11,700/11,500
Sensible Capacity (BTU/H) 7,930/7,630
Latent Capacity (BTU/H) 3,770/3,870
SEER 10.010.0
Dehumidification (Pints/H) 3.3/3.2
Amps (A) 5.5/5.9
Power Inputs (W) 1,210/1,180
HEATING
Total Capacity (BTU/H) 13,000/12,700
HSPF 6.8/6.8
Amps (A) 5.1/5.4
Power Inputs (W) 1,170/1,120
Back-up Strip Heater (KW) 1.50/1.23
Outdoor Sound Rating(bels) 7.0
FEATURE
Controls Microprocessor
Remote Controller LCD Wireless type
Temperature Control IC Thermostat
Timer ON/OFF, 24 hours
Night Setback Built-In
Air Louver (Horizontal) Manual
(Vertical) Automatic
Power Failure Automatic Restart Built-In
Self Diagnosis Built-In
Heating/Cooling Automatic Changeover Built-In
OPTION
Refrigerant Line Set AP1205BH (15 ft)
AP1207BH (20 ft)
AP1210BH (30 ft)
Low Ambient Control N/A
Fresh Air Intake N/A
Central Remote ON-OFF Control Available
Airduct Extension N/A
Indoor Frame Extension PLB182
Condensate Drain Pump Available
Non-Removable Remo-con Bracket Available
OPERATING RANGE
Cooling Indoor Air Outdoor Air
Intake Temp. Intake Temp.
Maximum 95 F DB/71 F WB 115 F DB
Minimum 67 F DB/57 F WB 67 F DB
Heating Maximum 80 F DB/67 F WB 75 F WB/65 F WB
Minimum - F DB/ - F WB 17 F WB/15 F WB
CERTIFICATION
12KHS32
AIRCONDITIONING PRODUCTS

Other manuals for Sanyo 12KHS32

Question and Answer IconNeed help?

Do you have a question about the Sanyo 12KHS32 and is the answer not in the manual?

Sanyo 12KHS32 Specifications

General IconGeneral
Model Number12KHS32
CategoryHeat Pump
Cooling Capacity12000 BTU/h
RefrigerantR410A
Noise Level (Indoor Unit)38 dB(A)
Net Weight (Outdoor Unit)34 kg
Noise Level (Outdoor Unit)52 dB(A)
Heating Capacity13000 BTU/h

Summary

General Data

Performance Data @ ARI Standard Conditions

Cooling Performance

Details cooling capacity, SEER, amps, and power inputs under standard conditions.

Heating Performance

Details heating capacity, HSPF, amps, power inputs, and sound rating.

Features and Controls

System Features & Controls

Describes system features like remote control, temperature settings, and automatic functions.

Options

Refrigerant Line Set Options

Lists available refrigerant line set lengths for installation.

Other Available Options

Details optional accessories and features like remote control and drain pump.

Operating Range

Cooling Operating Range

Specifies the acceptable indoor and outdoor temperatures for cooling operation.

Heating Operating Range

Specifies the acceptable indoor and outdoor temperatures for heating operation.

Certifications

Dimensional Data

Indoor Unit Dimensions

Provides detailed measurements for the indoor unit, including mounting and connection points.

Outdoor Unit Dimensions

Provides detailed measurements for the outdoor unit, including overall size and connection locations.

Warranty Information

Product Warranty Terms

Outlines the warranty period for the compressor and other components.

Manufacturer Contact

Provides contact details and website for SANYO FISHER COMPANY.

Related product manuals