Indoor Unit SAP-K127GHAX
Outdoor Unit SAP-C127GHAX
230 V Single Phase 50 Hz
29
RATING CAPACITY 3.55 kW
AIR FLOW RATE 470 m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP.
C OUTDOOR AMBIENT TEMP. C
W.B. D.B. 20 25 30 35 40 43
TC 3.58 3.42 3.27 3.11 2.92 2.69
CM 0.90 0.97 1.04 1.12 1.26 1.41
21 SHC 2.34 2.25 2.17 2.08 1.98 1.87
15 23 SHC 2.58 2.49 2.41 2.33 2.23 2.11
25 SHC 2.82 2.74 2.65 2.57 2.47 2.35
27 SHC 3.07 2.98 2.89 2.81 2.71 2.59
29 SHC 3.31 3.22 3.14 3.05 2.92 2.69
31 SHC 3.55 3.42 3.27 3.11 2.92 2.69
TC 3.84 3.67 3.50 3.34 3.14 2.89
CM 0.92 1.00 1.07 1.15 1.30 1.44
21 SHC 2.09 2.01 1.92 1.84 1.74 1.62
17 23 SHC 2.34 2.25 2.16 2.08 1.98 1.86
25 SHC 2.58 2.49 2.40 2.32 2.22 2.10
27 SHC 2.82 2.73 2.65 2.56 2.46 2.34
29 SHC 3.06 2.97 2.89 2.80 2.71 2.59
31 SHC 3.31 3.22 3.13 3.05 2.95 2.83
TC 4.08 3.91 3.73
3.55 3.34 3.07
CM 0.95 1.03 1.10 1.18 1.33 1.48
21 SHC 1.83 1.74 1.66 1.57 1.48 1.36
19 23 SHC 2.07 1.99 1.90 1.82 1.72 1.60
25 SHC 2.32 2.23 2.14 2.06 1.96 1.84
27 SHC 2.56 2.47 2.38 2.30 2.20 2.08
29 SHC 2.80 2.71 2.63 2.54 2.44 2.33
31 SHC 3.04 2.95 2.87 2.78 2.69 2.57
TC 4.33 4.14 3.95 3.76 3.54 3.25
CM 0.98 1.06 1.13 1.22 1.37 1.52
23 SHC 1.80 1.72 1.63 1.55 1.45 1.34
21 25 SHC 2.04 1.96 1.87 1.79 1.70 1.58
27 SHC 2.29 2.20 2.12 2.03 1.94 1.82
29 SHC 2.53 2.44 2.36 2.28 2.18 2.06
31 SHC 2.77 2.68 2.60 2.52 2.42 2.30
TC 4.59 4.39 4.19 3.95 3.70 3.44
CM 1.00 1.09 1.16 1.25 1.40 1.56
23 25 SHC 1.76 1.67 1.59 1.49 1.39 1.30
27 SHC 2.00 1.92 1.83 1.74 1.64 1.54
29 SHC 2.24 2.16 2.07 1.98 1.88 1.78
31 SHC 2.48 2.40 2.31 2.22 2.12 2.02
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35
C D.B.
Indoor Unit Entering Air Temp. 27
C D.B. / 19 C W.B.