8-27
Capacity Table
1
2
3
4
5
6
7
8
SPW-XDR254GXH56B
Power supply : 220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.3 kW AIR FLOW 20.0 m
3
/min
EVAPORATOR
AIR INTAKE. TEMP
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
23 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
25 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
29 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
TC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.7 6.5
21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3
29 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 5.9
31 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 7.0 6.8 6.6
21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.1 3.1 3.0
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.7 3.6
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.3 4.3
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 4.9
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.7 5.6 5.5
31 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.3 6.3 6.2
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8
23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.5 3.5 3.4 3.3 3.3
25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.5
29 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.3 5.2
31 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2 6.2 6.1 6.1 6.0 5.9 5.8
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.2 8.1 7.9 7.8 7.7 7.5 7.3 7.2 7.0
23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.1 3.1 3.0 2.9
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.5 4.4 4.3 4.3 4.2
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.9 5.9 5.8 5.7 5.7 5.6 5.6 5.5
TC 8.8 8.8 8.8 8.7 8.7 8.6 8.5 8.4 8.2 8.1 8.0 7.8 7.6 7.5 7.3
25 SHC 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.5 3.5 3.5 3.4 3.3 3.3
27 SHC 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9
29 SHC 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.5
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.4 5.3 5.3 5.2
TC 9.3 9.2 9.2 9.1 9.0 8.9 8.8 8.7 8.6 8.5 8.3 8.2 8.0 7.8 7.6
25 SHC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.1 3.1 3.0 2.9
27 SHC 4.2 4.2 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6
29 SHC 4.8 4.8 4.8 4.8 4.7 4.7 4.7 4.6 4.6 4.5 4.5 4.4 4.4 4.3 4.2
31 SHC 5.5 5.5 5.4 5.4 5.4 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9
CONDENSER
AMBIENT TEMP. (
o
C)
21
23
22
18
19
17
20
15
16
2. Cooling Capacity of Indoor Unit
TD831143-00W-3WAY.indb27TD831143-00W-3WAY.indb27 2008/12/0116:24:332008/12/0116:24:33