1-3. Other Component Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XM125 / 165 / 185H
MODEL No.
Indoor Unit SPW-XM125 / 165 / 185H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance
Ω
Thermal cut off temperature °C
Thermistor (Coil sensor): TH
PB2M-41E-S15-1
Resistance
kΩ
–10°C: 23.7±5% 20°C: 6.5±5%
–5°C: 18.8±5% 30°C: 4.4±5%
0°C: 15.0±5% 40°C: 3.1±5%
5°C: 12.1±5% 45°C: 2.6±5%
10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
KTEC-35-S98
Resistance
kΩ
0°C: 16.5±5% 40°C: 2.7±5%
5°C: 12.8±5% 45°C: 2.2±5%
10°C: 10.0±5% 50°C: 1.8±5%
20°C: 6.3±5% 55°C: 1.5±5%
30°C: 4.0±5%
Electronic expansion valve
Valve body
Coil
Drain pump
PLD-12230ST-2
Rated
AC230V 12W
Float switch
FS-0218-102
Rated (Contact rated)
Contact open at float rising
SM830160-03ClassicPAC-iA4.ind263263SM830160-03ClassicPAC-iA4.ind263263 2010/02/1610:26:362010/02/1610:26:36