EasyManua.ls Logo

Sanyo XM18AAB - Straight Equivalent Length of Joints; Additional Refrigerant Charge; System Limitations

Sanyo XM18AAB
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
1-9. System Limitations
Max. No. allowable connected outdoor units 3 *1
Max. capacity allowable connected outdoor units 288,000 BTU/h (30 hp, 84.3 kW)
Max. connectable indoor units 40
Max. allowable indoor/outdoor capacity ratio 50 – 130 %
*1: Up to 3 units can be connected if the system has been extended.
1-7. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 1-8 Straight Equivalent Length of Joints
Gas tubing size (in. (mm))
1/2"
(12.7)
5/8"
(15.88)
3/4"
(19.05)
7/8"
(22.22)
1"
(25.4)
1-1/8"
(28.58)
1-3/8"
(34.92)
1-5/8"
(41.28)
90° elbow
1 1.1 1.4 1.6 1.7 1.9 2.5 2.8
45° elbow 0.8 0.9 1 1.2 1.3 1.4 1.8 2.0
U-shape tube bent (R2-3/8" – 4" (60 – 100)) 3 3.4 4.1 4.7 5.1 5.6 7.4 8.4
Trap bend
7.5 9.2 10.5 12.5 14.1 15.4 19.2 22.3
Y-branch distribution joint Equivalent length conversion not needed.
Ball valve for service Equivalent length conversion not needed.
Table 1-9 Refrigerant tubing (Existing tubing can be used.)
Tubing size (in. (mm))
Material O Material 1/2H • H
ø1/4" (ø6.35) t1/32" (t0.8) ø7/8" (ø22.22) t5/128" (t1.0)
ø3/8" (ø9.52) t1/32" (t0.8) ø1" (ø25.4) t5/128" (t1.0)
ø1/2" (ø12.7) t1/32" (t0.8) ø1-1/8" (ø28.58) t5/128" (t1.0)
ø5/8" (ø15.88) t5/128" (t1.0) ø1-1/4" (ø31.75) t3/64" (t1.1)
ø3/4" (ø19.05) over t5/128" (t1.0) ø1-1/2" (ø38.1) over t3/64" (t1.15)
ø1-5/8" (ø41.28) over t3/64" (t1.20)
* When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.
1-8. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length and a type of outdoor unit as follows.
Liquid tubing size Amount of additional
(in. (mm)) refrigerant charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Required amount of additional refrigerant charge = [(Amount of additional refriger-
ant charge per ft. of each size of liquid tube × its tube length) + (...) + (...)] + [Nec-
essary amount of additional refrigerant charge per outdoor unit + (...) + (...)]
* Always charge accurately using a scale for weighing.
* If the existing tubing is used, and the amount of on-site additional refrigerant
charge exceeds the value listed below, then change the size of the tubing to
reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit :62 lbs
Max. additional charge for 2 outdoor units :111 lbs
Unit: ft.
Table 1-11 System Limitations
Table 1-10-1 Amount of Additional Refrigerant Charge Per ft., According to Liquid Tubing Size
Table 1-10-2 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
CHDX07263, CHDXR07263 CHDX09663, CHDXR09663
42 oz/unit 42 oz/unit

Table of Contents

Related product manuals