SBS-H2 Users Manual, Rev. 07-17-TNEMH2 Page 6 July 2017
4.0 Specifications
Dimensions
Main control: 4.7" L x 4.7" W x 1.2" D
Sensor: 3.1" L x 1.6" W x 0.87" D
Mounting
Wall: two 3/16" screws (not included)
H2-JB Junction box: 4 11/16" x 4 11/16" 2-gang junction box
Power Requirements/Options
Warning: Power requirements for the unit and relays should not exceed min/max specifications
120 Vac, 50/60 Hz Nominal (Terminal J8)
o 93 - 121 Vac
o 250mA / 10W Max
220 Vac, 50/60 Hz Nominal (Terminal J8)
o 185 - 242 Vac
o 125mA / 10W Max
12-48 Vdc Nominal (Terminal J9)
o 9 - 58 Vdc
o 600mA / 6W Max
o Note: An earth ground must be supplied to the GND terminal on the AC terminal block
when using only the DC power supply
Relays
1% Warning Relay (Terminal J6)
o 1 Normally Open and 1 Normally Closed contact
o Rated for 15 A resistive @ 120 Vac
o Rated for 10 A resistive @ 277 Vac
o Rated for 10 A resistive @ 28 Vdc
2% Alarm Relay (Terminal J3)
o 1 Normally Open and 1 Normally Closed contact
o Rated for 0.5A @ 28 Vdc
Temperature/Humidity
Operating Temperature Range: 32°F (0°C) to 122°F (50°C)
Operating Humidity Range: 20-95% non-condensing
Storage Humidity Range: 5-95% non-condensing
Maximum Altitude
2000 meters
Audible Alarm
85 dB at 10’ @ 1.6 - 3.2 KHz
Strobe LED
146 lumens at 1A @ 3.2-4.2V