TechnicalInstructions TSSeries
DocumentNo.TS6500
Page2SCCInc.
Features
ConvertsnativeModbus/RTUtoProfinetorProfibus
o DatapointsforLMV3...
o DatapointsforLMV5...
o DatapointsforRWF...
o DatapointsforTSSeriesTouchscreenKit
o DatapointsforTSSeriesLead/LagMaster
o DatapointsforTSSeriesLead/LagMaster(fromeach
boiler)
o DatapointsforTSSeriesDeaerator/SurgeTankMaster
Allowssimultaneousconnectionofupto6devicesviaserial
connectionsandupto12devicesviaEthernetModbus
TCP/IPconnections
Application
TS…protocolconverterkitsaresuitedforapplicationswithProfinet
orProfibusBMScommunication.AllSCCproductsthatcommunicate
usingModbus/RTUarecompatible.
Components
AllTS…protocolconverterkitsincludethefollowingcomponents:
Protocolconvertermodule
Platekitincludingpowersupplyandbranchcircuit
protection
Interconnectterminalsforfieldwiring
Fieldportforvariousprotocols
Thefollowingoptionsarealsoavailable:
HostportforModbusRTURS232
HostportforModbusRTURS485
Ethernetswitchtosupportupto12TS…seriesTCP/IP
devicesviaEthernettoBMS

Other manuals for SCC TS Series