EXPLOSIONPROOF
Throttle valve Original view InMax-..-.F1
Air Damper
Ball valve
Compact. Easy installation. Universal. Cost effective. Safe.
Subject to change!
InMax – Revolution
Electrical, industrial quarter turn actuators size S
On-off, 24…240 VAC/DC, 95° angle of rotation
Fast spring return < 1 sec.
Industrial actuators, IP66 protection
Universal supply unit from 24 to 240 VAC/DC
Circuit for directly connection of a InPro-TT-.. sensor (option -BF1)
2 integral aux. switches, switching at 5° and 85° angle of rotation (option -SF1)
5 different motor running times (3-15-30-60-120 sec./90°), adjustable on site
Spring return running time < 1 sec./90°
On-off control with spring return function
100 % overload protected, selflocking
Compact design and small dimension (L × W × H = 210 × 95 × 80 mm)
Direct coupling to the damper shaft with double-squared connection 12 × 12 mm
95° Angle of rotation incl. 5° pre-tention
Robust aluminium housing (optional stainless steel or amercoat painting)
Simple manual override include + preparation for comfortable manual override
Gear made of stainless steel and sinter metal
Weight only 3,5 kg
Integral heater for ambient temperatures down to -40°C
Integral safety temperature sensor
Integral equipment for manual adjustment (push button, lamp, switch)
Preparation for adaptable aux. switches (type InSwitch)
Range of accessories
Type Torque Supply Motor running time Spring return Control mode Additional features Wiring diagram
InMax-8-F1 8 Nm 24..240 VAC/DC 3/15/30/60/120 sec. at 90° < 1 sec. at 90° On-off SB 1.4/1.5
InMax-8-SF1 8 Nm 24..240 VAC/DC 3/15/30/60/120 sec. at 90° < 1 sec. at 90° On-off 2 contacts (5/85°) SB 1.4/ 1.5
InMax-8-BF1 8 Nm 24..240 VAC/DC 3/15/30/60/120 sec. at 90° < 1 sec. at 90° On-off 2 contacts (5/85°) + fire trigger SB 7.5/ 7.6
InMax-15-F1 15 Nm 24..240 VAC/DC 3/15/30/60/120 sec. at 90° < 1 sec. at 90° On-off SB 1.4/1.5
InMax-15-SF1 15 Nm 24..240 VAC/DC 3/15/30/60/120 sec. at 90° < 1 sec. at 90° On-off 2 contacts (5/85°) SB 1.4/ 1.5
InMax-15-BF1 15 Nm 24..240 VAC/DC 3/15/30/60/120 sec. at 90° < 1 sec. at 90° On-off 2 contacts (5/85°) + fire trigger SB 7.5/ 7.6
InMax-…-VAS Type as above but with stainless steel housing (AISI 316) gearbox parts in stainless steel, cable gland and hollow rivet nickel-plated
InMax-…-CTS Type as above but with aluminium housing and Amercoat paint, gearbox parts, cable gland and hollow rivet nickel-plated
InMax- 8 - F1
InMax- 8 - SF1
InMax- 8 - BF1
InMax- 15 - F1
InMax- 15 - SF1
InMax- 15 - BF1
InMax- ... - ... - VAS
InMax- ... - ... - CTS
Description size S
The InMax actuators are a revolution for safety, fire and shut-off
dampers other motorized applications in chemical, pharmaceutical,
industrial and Offshore-/Onshore plants, for use in safe areas.
IP66 protection, small dimensions, only 3,5 kg weight, universal
functions and technical data, an integrated heater and an optional
stainless steel housing guarantee safe operation even under difficult
environmental conditions. High quality brushless motors guarantee
long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times selectable or
adjustable on site. The integrated universal power supply is self
adaptable to input voltages in the range of 24 to 240 VAC / DC.
The actuators are 100% overload protected.
InMax-...-F1 actuators are equipped with spring return fail safe function.
Futher the InMax-..-SF1 with integrated aux. switches for end position
indication and the InMax-..-BF1 with an additional circuit to connect an
external passive potential free thermostat Type InPro-TT-... Standard
shaft connection is a double squared direct coupling with 12 × 12 mm.
Different accessories are available to adapt aux. switches, terminal
boxes or adaptations for ball valves and throttle valves.
Application
Highlights

Other manuals for Schischek InMax Revolution

Question and Answer IconNeed help?

Do you have a question about the Schischek InMax Revolution and is the answer not in the manual?

Summary

InMax Actuator Overview

Key Highlights and Features

Lists key features like universal supply, integral aux. switches, adjustable motor running times, and robust construction.

Technical Data and Certifications

InMax Actuator Specifications

Detailed technical specifications for InMax-8-.F1 and InMax-15-.F1 models, covering torque, voltage, and dimensions.

Electrical Connections and Parameter Settings

InMax Actuator Connection Schematics

Illustrates various electrical connection methods for InMax actuators, including On/Off and spring return configurations.

Parameter Adjustment and Failure Indication

Explains how to adjust actuator parameters, failure indications, and the function of control elements like switches and LEDs.

Mounting and Installation Guidelines

Extra Information EL-S: Power Supply

Power Supply Design for InMax Actuators

Details power supply design for InMax actuators, including voltage ratings and current consumption based on motor running time.

Error Indication and Operational Notes

Troubleshooting InMax Actuator Errors

Lists common errors, their reasons, and solutions for InMax actuators, focusing on LED indicators and operational faults.

Mounting Instructions for Air Dampers

Schischek InMax Revolution Specifications

General IconGeneral
BrandSchischek
ModelInMax Revolution
CategoryController
LanguageEnglish

Related product manuals