RedMax - ... - F3
RedMax - ... - SF3
RedMax - ... - BF3
RedMax - ... - CTM
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
RedMax-M-F3_en
V01 – 19-Sep-2016
Subject to change!
Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description Highlights
Fire damper Ball valve Throttle valve
Electrical, explosion proof rotary actuators with integrated Ex-i circuit (optional)
On-off / 3-pos. control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension
30 – 50 Nm with safety operation (spring return), optional with limit switches
ATEX tested in acc. with directive 2014/34/ EU for zone 2, 22
RedMax ¼ turn actuators – size M
► For all type of gas, mists, vapours and dust for use in zone 2 and 22
► Universal supply unit from 24…240 VAC/DC
►Motor running times 40– 60–90 –120–150 s /90° adjustable on site
► On-off control with spring return function, running time ≤ 3 s/90°
► Ex-i circuit for direct connection of the ...Pro-TT-... safety temperature trigger
(type ...-BF3)
► 2 integrated auxiliary switches, switching at 5° and 85° angle of rotation
► 30– 50 Nm actuators in the same housing size
► 100 % overload protected
► Compact design and small dimension (L × W × H = 288 × 149 × 116 mm)
► Direct coupling to the damper shaft with double square connection 16 × 16 mm
► 95° angle of rotation inclusive 5° pretension
► Robust aluminium housing (optional with seawater resistant coating)
► IP66 protection
► Simple manual override included + preparation for comfortable manual override
► Gear made of stainless steel and sinter metal
► Weight only ~ 9,5 kg
► Integral heater for ambient temperatures down to −40 °C
► Integral safety temperature sensor
► Integral equipment for manual adjustment (push button, lamp, switch)
► Preparation for adaptable and adjustable auxiliary switches type ...Switch
► Wide range of accessories
The RedMax actuators are a revolution for safety, fire and shut-off dampers,
VAV systems, ball valves, throttle valves and other motorized applications
for HVAC systems in chemical, pharmaceutical, industrial and offshore/onshore
plants, for use in Ex-areas zone 2 (gas) and zone 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions,
only 9,5 kg weight, universal functions and technical data, an integrated
heater guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. The actuators are
100 % overload protected.
...Max-...-F3 actuators are equipped with spring return fail safe function.
Additionally the ...Max-...-SF3 and ...-BF3 actuators are equipped with
2 integrated, potential free auxiliary switches each and ...Max-...-BF3
comes with an intrinsically safe trip circuit for connecting the ...Pro-TT-...
safety temperature trigger. Standard shaft connection is a double square
direct coupling with 16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Type Torque Supply Motor running time Spring return Control mode Feedback Wiring diagram
RedMax- 30 - F3 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ≤ 3 s/90° On-off – SB 2.4 + 2.5
RedMax- 50 - F3 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ≤ 3 s/90° On-off – SB 2.4 + 2.5
RedMax- 30 - SF3 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ≤ 3 s/90° On-off 2 × limit switches SB 2.4 /2.5 + 3.2
RedMax- 50 - SF3 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ≤ 3 s/90° On-off 2 × limit switches SB 2.4 /2.5 + 3.2
RedMax- 30 - BF3 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ≤ 3 s/90° On-off 2 × limit switches + Ex-i trip circuit SB 2.4/2.5 +3.2 +7.4
RedMax- 50 - BF3 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ≤ 3 s/90° On-off 2 × limit switches + Ex-i trip circuit SB 2.4/2.5 +3.2 +7.4
RedMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
1 / 4