EasyManua.ls Logo

Seifert 43301001 - User Manual

Seifert 43301001
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Version Nr. 1-3 - 11.07.2022 Doc. No. 9943301001 1 / 17
Table of Content 43301001
1. User manual 2 ..................................................................................................................................
2. Legal regulations 2 .........................................................................................................................
3. Safety instructions 3 ......................................................................................................................
4. Settings 4 .........................................................................................................................................
5. Functional principle 5 .....................................................................................................................
6. Technical data 6 ..............................................................................................................................
7. Performance graph 7 ......................................................................................................................
8. Mounting 8 .......................................................................................................................................
9. Mounting Principle 9 .......................................................................................................................
10. Cut out dimensions 10 ..................................................................................................................
11. Dimensions (H x W x D) 11 ..........................................................................................................
12. Electrical connection 12 ...............................................................................................................
13. Controller 13 ..................................................................................................................................
14. Wiring diagram 14 .........................................................................................................................
15. Taking into operation 15 ..............................................................................................................
16. Trouble shooting 15 ......................................................................................................................
17. Maintenance & Cleaning 15 .........................................................................................................
18. Transport & Storage 16 ................................................................................................................
19. Parts supplied / Spare parts / Accessories 17 ..........................................................................
Question and Answer IconNeed help?

Do you have a question about the Seifert 43301001 and is the answer not in the manual?

Overview

This document describes the Seifert cooling unit, model 43301001, an industrial accessory designed for dissipating heat from electrical control cabinets and similar enclosures to protect sensitive components. It is not intended for household use. The unit ensures that clean cabinet air does not come into contact with ambient air, which may be dirty or polluted, through two completely separate air circuits. It can function effectively in extreme ambient conditions, such as dusty and oily air, with a standard operating temperature range of 50°F to 131°F. Units can also be ordered with an additional electrical cabinet heater.

Function Description:

The cooling unit operates on a functional principle involving a refrigeration circuit with a compressor, evaporator, condenser, and expansion device. It uses R134a refrigerant, which is chlorine-free and has a low Ozone Depletion Potential (ODP) and Global Warming Potential (GWP). The compressor compresses the refrigerant, raising its pressure and temperature. This hot, high-pressure gas then passes through the condenser, where it is cooled by ambient air and condenses into a liquid state. The liquid refrigerant then flows through a capillary pipe, reducing its pressure before reaching the evaporator. In the evaporator, the refrigerant absorbs heat from the cabinet air, causing it to evaporate and change back into a gas. This process cools the cabinet air. The gas is then drawn back into the compressor, completing the cycle.

For condensation management, in environments with high humidity and low internal enclosure temperatures, condensation may form on the evaporator coil. Standard cooling units include a drain hose at the bottom of the unit for connection to a drain pipe. Units with condensate evaporators have an internal evaporator based on self-regulating PTC cartridges. Condensate is drained to an internal recipient where it evaporates when in contact with the cartridge surface. The resulting steam is directed towards the condenser, and the PTC heater cartridge is permanently connected. The recipient has an overflow socket at the bottom of the unit, for which a drain pipe is supplied.

The unit can be switched on and off via a door contact switch. When delivered, the door contact terminals are bridged on the female connector. To connect a door contact switch, the bridge must be removed, and the switch connected. The contact must be closed when the cabinet door is closed.

Important Technical Specifications:

  • Order Number: 43301001
  • Cooling Capacity:
    • 95F/95F: 10,240 BTU
    • 95F/122F: 8,260 BTU
  • Compressor Type: Rotary piston compressor
  • Refrigerant: R134a / GWP 1430
  • Refrigerant Charge: 900 g / 31.7 oz
  • High / Low Pressure: 29.5 / 6 bar (425 / 88 psig)
  • Operating Temperature Range: 50°F - 131°F
  • Air Volume Flow (system / unimpeded):
    • Ambient air circuit: 441 / 706 cfm
    • Cabinet air circuit: 506 / 706 cfm
  • Mounting: External
  • Housing Material: Mild steel, powder coated
  • Dimensions (H x W x D): 48.4 x 19.7 x 13.4 inch
  • Weight: 165 lbs.
  • Cut Out Dimensions: 44.48 x 16.92 inch
  • Voltage / Frequency: 120 V ~ 60 Hz (UL: 115 V ~ 60 Hz)
  • Current (95F95F): 15.3 A
  • Starting Current: 49 A
  • Max. Current: 18.4 A
  • Nominal Power (95F95F): 1.37 kW
  • Max. Power: 1.65 kW
  • Fuse: 20 A (T)
  • Short-Circuit Current Rating (SCCR): 5 kA
  • Connection: Connection terminal block
  • Ingress Protection: TYPE 12
  • Approvals: CE, CURus, cULus

Usage Features:

The unit is pre-set at 95°F, which is suitable for most electronic devices. The controller allows for adjustment of the cooling set point (St/St1) between 68°F and 122°F. To change the set point:

  1. Press 'Set' until St/St1 appears on the display.
  2. Press the Up/Down buttons to adjust the temperature setting.
  3. Press 'Set' to save the new setting. For units with internal heaters, the heating set point (St2) can also be adjusted:
  4. Press 'Set' until St1 appears on the display and release the button.
  5. Press again 'Set' till St2 appears on the display.
  6. Press the Up/Down buttons to adjust the temperature.
  7. Press set to save the new setting. It is important to ensure that St2 (set point + 5K) is less than St1. The unit also features a potential-free high-temperature alarm relay that triggers if the enclosure temperature exceeds 131°F.

Mounting:

The power supply rating on the unit rating plate must comply with mains rating. Always disconnect the power supply before opening the unit. The heat load to be dissipated from the enclosure should not exceed the specific cooling output of the unit at any condition. Cooling unit selection should always allow for a safety margin of at least 15% extra cooling output in the worst conditions. Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. It must also be ensured that the air outlet is not blowing air directly at an equipment operator. Should this be the case, a barrier or duct should be provided to redirect the airflow. The cooling unit enclosure air suction hole must be installed in the highest possible point. When installing the unit on a door, ensure it can take the weight. Before drilling the enclosure, ensure that fixing elements and couplings will not interfere with the equipment inside the enclosure itself. Disconnect power before starting any work inside the enclosure. A drilling template is provided, and the required cuts on the enclosure must be made. The sealing strip on the cooling unit must be fitted to the enclosure to ensure proper sealing. Do not use the unit within the first 15 minutes after installation to allow for adequate lubrication of the compressor.

Maintenance Features:

The cooling unit is generally maintenance-free and can be operated without filters in most environments. For units with filters, these should be checked, cleaned, and if necessary, replaced regularly. The unit should also undergo regular functional tests (approximately every 2,000 hours, depending on ambient pollution). Always switch off the power supply before starting any maintenance.

Troubleshooting:

The manual provides a troubleshooting guide for common issues:

  • Internal fan does not work: Check power supply.
  • Unit doesn't cool (internal fan works, external fan and compressor don't work): Verify controller set point (St1), check door switch contact, replace controller.
  • Unit doesn't cool (internal fan works, external fan and compressor don't work, display shows alternating OFF and temperature): Correct phase sequence in power supply connector.
  • Unit doesn't cool (external and internal fan work, compressor does not work): Replace compressor by qualified service technician, replace capacitor.
  • Unit doesn't cool (compressor works, external fan doesn't work): Replace external fan.
  • Enclosure temperature too hot (compressor and fans work all the time): Enclosure needs a cooling unit with higher capacity.
  • Enclosure temperature too hot (compressor and external fan work in alternating mode): Verify ambient temperature, clean condenser, contact dealer/service center for refrigerant leakage.
  • Excessive condensate (enclosure door open): Ensure door is closed, add a door switch and connect to controller.
  • Excessive condensate (enclosure door closed): Seal all openings of the enclosure, repair damaged or misplaced sealing strip.

Transport & Storage:

The unit contains R134a refrigerant and small quantities of lubricating oil. Replacement, repairs, and final disposal must be done according to the regulations of each country for these substances.

  • Malfunction due to transport damage: The carton box must be examined for signs of transport damage upon delivery. Any transport damage that could indicate a unit malfunction must be reported.
  • Storage conditions: The unit can only be stored in locations meeting the following conditions:
    • Temperature range: -40°F to 158°F
    • Relative humidity (at 77°F): max. 95%
  • Returning the unit: To avoid transport damage, the unit should be returned in its original packing or in a packing case and must be strapped to a pallet. If the unit cannot be returned in original packing, ensure:
    • A space of at least 30 mm is maintained at all points between the unit and the external packing.
    • The unit is shipped in the same position as it was mounted.
    • The unit is protected by shock-resistant padding (hard foam corner pieces, strips or cardboard corner pieces).

Parts Supplied / Spare Parts / Accessories:

The unit comes with an instruction manual, CE Declaration, mounting template, M6*16 bolts, A6.4 washers, M6 toothed washers, lifting hook M8 x 12, PVC washer, drain pipe, female connector, and foam tape. Available accessories include fibre filter media EU2 (SP-43250001-O-1), washable aluminium filter (SP-43250001-BF-1), stainless steel filter holder incl. filter media (SP-43250001-BG-1), and a door contact switch (3100001).

Seifert 43301001 Specifications

General IconGeneral
BrandSeifert
Model43301001
CategoryAccessories
LanguageEnglish

Related product manuals