SERVICE | Apendix A
Product Specications
SP PRO SERIES SPECIFICATIONS SPMC 240–AU SPMC 241–AU SPMC 481–AU SPMC 482–AU SPMC 1201–AU SPLC 1201-AU
Nominal battery voltage 24 V 24 V 48 V 48 V 120V 120V
Continuous, output power
Continuous, charge current
@ 25°C
2,800 W
105 A
4,000 W
146 A
4,500 W
83 A
7,000 W
125 A
7,000 W
50 A
18,000 W
125 A
Continious grid export power rated output
20 second load rating
20 second output current
@ 40°C
7,500 W
28 A
10,500 W
40 A
12,000 W
47 A
18,000 W
70 A
18,000 W
70 A
30,000 W
125 A
1 minute output power @ 40°C 5,400 W 7,600 W 8,700 W 13,000 W 13,000 W 25,000 W
60 minute output power @ 40°C 3,200 W 4,700 W 5,300 W 8,000 W 8,000 W 19,000 W
DC input voltage range 20 - 34 V 20 - 34 V 40 - 68 V 40 - 68 V 100 - 170 V 100 - 170 V
TRANSFER SWITCH (Synchronous)
AC transfer current capacity 63 A 125 A
Max AC input source, (generator/grid) 15 kVA 30 kVA
Max total output to Load, AC source + inverter 15 kVA 30 kVA
AC transfer time no-break
If grid fails 0 - 0.03 seconds
Battery charger type Temperature compensated, 5 stage, power factor corrected with dual stage oat
EFFICIENCY
DC consumption idle 6 W
DC consumption standby (Econo Mode) 12 - 20 W n/a
ON with no load 31 W 36 W 37 W 40 W 38 W 75 W
Peak eciency – all modes 95% 95% 95.5% 96% 96.5% 96%
10% load 90% 90.5% 91% 91% 91.5% 91%
20% load 92.5% 93% 94% 94% 94% 94%
50% load 94% 94.5% 95% 95.5% 96% 95.5%
100% load 90% 91% 92.5% 93% 93.5% 93%
AC OUTPUT (standalone)
Range 210 to 240 V+/- 0.5%
Regulation <1% droop 0-100% rated load (<2% @ 150%, <5% @200%)
THD <3% @ 0-200% rated load
Frequency 50 or 60 Hz +/-0.005% standalone
AC SOURCE (input)
Nominal voltage 240 V~
AC current (Recharge, Bypass & Normal modes) 63 A 125 A
Tolerance on nominal voltage installer programmable 204 to 264 V~
Nominal input frequency 50/60 Hz
Tolerance on nominal frequency installer programmable +/- 1% to 10%
Generator can be started by battery SoC, DC voltage, battery load, unit temperature, time & remote control
FEATURES
Battery temperature sensor Included
Mid point battery voltage sensing Included
Inverter display 22 x LEDs with auto adjusting intensity.
Display indicates, charger status, remaining useable battery capacity, alarms, AC status.
AC status LEDs powered from AC voltage.
Generator control button. Output mode button. Alarm silence button.
Digital Inputs 4 o: Max 60 VDC ( Active > +6 V, Inactive < +3 V )
Shunt Inputs 2 o: +/-75 mV, adjustable 25 A to 500 A
Analogue Inputs 2 general purpose logged 0-60 V n/a
Relay Outputs 4 o: 60 V, 500 mA
Digital outputs 3 o: 60 V, 5 mA
Communication ports 2 o RS232 with adjustable baud rate of up to 57600
Memory retention of settings & data permanent
SP LINK conguration and monitoring software Standard, allows conguration of parameters or customer can view LED display remotely.
Dimensions (mounted) 345 W x 545 H x 215 D
520 W x 870 H x
300 D
Weight 29 kg 34 kg 35 kg 40 kg 40 kg 105 kg
Circuit Breakers (AC Source, AC Load) double pole 63 A
single pole 125 A
Standards AS 62040.1.1-2003, CE pending
AS/NZS 61000-6-3 2007 AS/NZS 61000-6-4 2007
Grid Protection AS 4777 2005 AS 4777 2005 pending
Protection IP43