ENGLISH
Pag. 7
4. Layout and conguration
1 2
1 2
*
*
3 4
3 4
*
*
5 6
5 6
*
*
** NNOOTTEE ::AALLLL IINNDDIICCAATTIIOONNSS GGIIVVEENN OONN RREELLAAYY CCOONNTTAACCTTSS AARREE MMEEAANNTT FFOORR NNOONN--CCOONNNNEECCTTEEDD CCAARRDD
SET ALL
SET R2
SET R3
S2 S1 FA WD ON
R3
R2
R1(FA)
12
3
4
5
6
Relay R1 (Fault or watch-dog relay)
Relay R2 (Alarm1 or Alarm2)
Jp1
Jp2 JP3
SET-ALL
OPEN: NORMALLY ENERGIZED RELAY (DEFAULT)
CLOSED: NORMALLY DE-ENERGIZED RELAY
SET-R2
RELAY R2 COUPLED TO THRESHOLD 1 (DEFAULT)
RRELAY R2 COUPLED TO THRESHOLD 2
SET-R3
RELAY R3 COUPLED TO THRESHOLD 2 (DEFAULT)
RELAY R3 COUPLED TO THRESHOLD 3
Jp3
WITH JUMPER BETWEEN 1 AND 2: NORMALLY CLOSED (NC) CONTACT OF THE R1 RELAY
WITH JUMPER BETWEEN 2 AND 3: NORMALLY OPEN (NO) CONTACT OF THE R1 RELAY
(DEFAULT)
Jp2
WITH JUMPER BETWEEN 1 AND 2: NORMALLY CLOSED (NC) CONTACT OF THE R2 RELAY
WITH JUMPER BETWEEN 2 AND 3: NORMALLY OPEN (NO) CONTACT OF THE R2 RELAY
(DEFAULT)
Jp1
WITH JUMPER BETWEEN 1 AND 2: NORMALLY CLOSED (NC) CONTACT OF THE R3 RELAY
WITH JUMPER BETWEEN 2 AND 3: NORMALLY OPEN (NO) CONTACT OF THE R3 RELAY
(DEFAULT)
LAYOUT
STS3REL
Relay R3 (Alarm2 or Alarm3)