Page #5 background image
Specifi cations
Kit Number 6-120
(Includes 8-120 Sensor Transmitter & 8-121 Receiver Display)
Range of Operation
Voltage 0 - 69kV
Current 1 - 5000A
Frequency
50Hz Calibrated 47 to 53Hz
60Hz Calibrated 57 to 63Hz
Sensor Opening Width 2.5 in, 6.35 cm
Resolution
Amps 1 - 99.9A 0.1A
Amps 100 - 50000A 1A
Accuracy ± 1% ± 2 Digits
Operation Controls Single button operation
Mechanical
Weight
Operating Temperature -4° to +140°F, -20° to +54° C
Storage Temperature -140° to +158°F, -40°C to +70° C
Display Five Digit Display
Type of Reading Four Readings
Housing Shock & Water resistant molded urethane
Hotstick Mounting Universal Chuck Adapter (Hotstick not included)
Battery 9 volt (1 ea in Transmitter & Receiver)
Battery Life Five days continuous use
Indoor/Outdoor Use
Relative Humidity 90% non-condensing
Altitude 3000 meters
Radio
Frequency Region One 869.85MHz
Frequency Region Two 916.48MHz
Frequency Region Three 916.48MHz
Power 1 miliwatt
Range 50 feet, 15.24 meters