19 -0 Indoor unit fan Indoor unit fan error (1) Check the indoor fan 
motor for proper rotating 
operation.(Check fan 
lock.)
(1) Replace the indoor fan 
motor.
(2) Check the lead wire of the 
indoor fan motor for open-
circuit.
(2) Replace the indoor fan 
motor.
(3) Check CN1 of the indoor 
unit fan motor for secure 
installation.
(3) Correct the installa-
tion of CN1 of the 
indoor fan motor.
(4) No abnormality found in 
above inspections (1) 
through (3).
(4) Replace the indoor 
unit control PWB.
Indoor/
outdoor 
units in 
operation
20 -0 Indoor unit con-
trol PCB
EEPROM data error (EEPROM read data 
error)
Replace the indoor 
unit control PWB.
Indoor/
outdoor 
units in 
operation
88 Control and dis-
play PCB
Communication 
error
(1) Check for disconnected 
connector between control 
PCB and display PCB, 
and open-circuit in lead 
wires.
(1) Insert connectors cor-
rectly, or replace con-
trol PWB.
(2) Check that control PCB 
outputs signals correctly.
(2) Replace control PWB.