CHAPTER 1. PRODUCT SPECIFICATION
[1] SPECIFICATION
1. AH-129 / AU-129
ITEMS
INDOOR UNIT
OUTDOOR UNIT
A
H-129
AU-129
Cooling capacity kW 3.50
Moisture removal Liters/h
Electrical data
Phase Single
Rated frequency Hz
50
Rated voltage V 220
Rated current
A5.1
Rated input * W 1090
Power factor % 97 - 99
Compressor Type Hermetically sealed rotary type
Model RH207VXGT
Oil charge 520cc (DIAMOND MS56)
Refrigerant system Evaporator Slit fin and Grooved tube type
Condenser Slit fin and Grooved tube type
Control Capillary tube
Refrigerant volume 960g
Noise level
High
dB(A)
39
48
Mid.
dB(A)
33
Low
dB(A)
29
Fan s
y
stem
Drive Direct drive
Air flow quantity
High
m3
/
min.
10.2
27
Mid.
m3
/
min.
9.6
Low
m3
/
min.
8.7
Fan
Cross flow fan
Propeller fan
Connections
Refri
g
erant cou
p
lin
g
Flare t
yp
e
Refri
g
erant tube size Gas, Li
q
uid 3
/
8" , 1
/
4"
Drain piping
mm O.D 18
Others
Safety device Compressor : Internal protector
Fan motor : Thermal fuse / Protector
Fuse, Micro computer control
Air filters Polypropylene net (Washable)
Net dimensions
Width
mm
790
730
Height
mm
278
540
Depth
Net weight
mm
kg
198
10
250
34
2