WARNINGS
TheSHIELDSprinklers mustbeinstalled andmaintained
incompliancewiththisdocument.Depressurizeanddrain
the piping system before attempting to install, remove,
oradjustanySprinklers.Failuretodosomayimpairthe
performanceofthesesprinklers.Theownerisresponsible
formaintaining the re protection systemand devicesin
operation.
WRENCH DESCRIPTION
The Sprinkler Wrench is a tool specically designed for
installingSHIELDSprinklers.Thesespecialwrenchesmust
be used to provide the proper leverage when tightening the
sprinklerandtominimizeslippageduringinstallation.Any
otherwrenchmaydamagethesprinkler.
INSTALLATION
All SHIELD Sprinklers must be installed according to
NFPA 13 Standards. Deviations fromthese requirements
and standards or any alteration to the sprinkler itself will
void any warranty made by manufacturer. In addition,
installation must also meet local government provisions,
codesandstandardsasapplicable.
The system piping must be properly sized to insure the
minimumrequiredowrateatthesprinkler.Checkforthe
proper model, style, orice size and temperature rating
prior to installation.Installsprinklersafterthepipingisin
place to avoid mechanical damage, replace any damaged
units.Wetpipesystemsmustbeprotectedfromfreezing.
Upon completion of the installation, the system must be
testedperrecognizedstandards.Intheeventofathread
task, remove the unit, apply new pipe joint compound or
tape,andreinstall.
ADDITIONAL
Cover Plate - To install the conceal cover plate, align it
with the sprinkler and slowly turn clockwise for the cover
platesandsprinklertolockin.Makesurethecoverplateis
securely locked in, fail to do so may cause the sprinkler to
malfunction.
INSTALLATION SEQUENCE
Step1.TheunitmustbeinstalledinthePendentposition
fortheConcealedSprinkler.
Step2.Useonlyanon-hardeningpipejointcompoundor
tapeseal.Applyonlytothemale
threads.
Step3.Handtightenthesprinklerintotting.
Step4.ForConcealedSprinklers,useastandardwrench.
Tightentheunit intothetting.A lead-tightjointrequires
only 7 to 14ft.-lbs(9.5 to 19.0Nm) oftorque. A tangential
force of 14 to 28ft.-lbs(62.3 to124.5N) delivered through
a 6”(150mm) handle will deliver adequate torque. Once
torque level reach over 21ft.-lbs(28.6Nm) it may distort
the orice seal, resulting in leakage. For exposed piping
systems, the sprinkler should be oriented so the frame
armsareparallelwiththebranchlinepipe.
CAUTION
Do not over-tighten or under-tighten the sprinkler to
compensateforinaccurateescutcheonplateadjustment.
Protectioncapsareusedtoprotectitsbulbanddeector.
Please have cap on at all times during transportation and
interiordecorating.
MAINTENANCE
Sprinklers must never be altered after manufacture. Any
alteration such as painting and coating will directly harm
thesprinklerandcausemalfunctions.Sprinklerincontact
with corrosive products should be replaced if they cannot
becleanedcompletely.
Visual inspections are recommended after installation.
After installation, a close-up inspection annually will
sufce.
Inspection and maintenance of re protection system is
the responsibility of the owner. It is recommended that
automatic sprinkler system be inspected and tested
accordingtolocaland/ornationalregulations.