MODEL: SD1010, SD1015, SD1030, SD1032
DESCRIPTION
The SHIELD Sprinklers, SD1010, SD1015, SD1030, SD1032
(Glass Bulb Type), Standard Orice, Upright, Pendent and
Recessed Pendent type, design incorporates state-of-the-art,
heat responsive, frangible glass bulb design (standard or quick
response)forprompt,preciseoperation.
The die cast frame is more streamlined and attractive than
traditionalsandcastframes.Itiscastwithahex-shapedwrench
boss to allow easy tightening from many angles, reducing assembly
effort. This sprinkler is available in various temperature ratings
and nishes to meet many design requirements. The recessed
pendent should be utilized with a recessed escutcheon which
provides up
”of adjustments. AllSprinklersaremanufactured
usingthetimeprovenBellevillesealusedexclusivelybyallmajor
manufacturestoensurelonglifeandsafeoperation.
SPRINKLER OPERATION
Theoperatingmechanismisafrangibleglassbulbwhichcontains
aheatresponsive liquid. Duringare, theambienttemperature
risescausingtheliquidinthebulbtoexpand.Whentheambient
temperature reaches the rated temperature of the sprinkler, the
bulbshatters. Asaresult, thewaterwayis clearedofallsealing
partsandwaterisdischargedtowardsthedeector.Thedeector
is designed to distribute the water in a pattern that is most
effectiveincontrollingthere.
MAXIMUM COVERAGE
Standard spray coverage is up to: Light Hazard = 225 square
feet(20.9sq.m);OrdinaryHazard=130squarefeet(12.1sq.m)per
NFPA13.
TECHNICAL SPECIFICATION
RATINGS
SPRINKLER HEAD
Upright, Pendent & Recessed Pendent Sprinklers
SprinklerIdentication
Number
Standard SD1015, SD1010
(bulb5mm),QuickResponse
SD1030,SD1032(bulb3mm)
Style Upright Sprinkler SD1015,
SD1032, Pendent &
Recessed Pendent
SD1010, SD1030
K Factor 5.6gpm/psi
½
.(80lpm/bar
½
)
ResponseTimeIndex
(RTI)
Standard 50
Quick Response 30
NominalThreadSize
½
”NPT(15mm)
OrceSize 13mm
Max.WorkingPressure 175PSI(1200kPa)
FactoryHydrostaticTest 100%@500PSI(3450kPa)
Min.OperationPressure 7PSI(48kPa)
SprinklerTemperature
Classication
Norminal Sprinkler
TemperatureRating
N.F.P.AMaximumAmbient
(Ceiling)Temp.(Allowed)
Glass Bulb Color
Ordinary** 155ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
High* 286ºF/141ºC 225ºF/107ºC Blue
ExtraHigh* 360ºF/182ºC 300ºF/149ºC Mauve
Open* Open - No Bulb
*Non-Approved
**ULListedonly.

Other manuals for Shield SD1010

Question and Answer IconNeed help?

Do you have a question about the Shield SD1010 and is the answer not in the manual?

Summary

SHIELD Upright, Pendent & Recessed Pendent Sprinklers

Description

Details the design, features, and materials of the SHIELD Upright, Pendent, and Recessed Pendent sprinklers.

Sprinkler Operation

Explains the heat-responsive glass bulb mechanism and water discharge process during a fire.

Maximum Coverage

Specifies the standard spray coverage areas for Light and Ordinary Hazard classifications per NFPA 13.

Ratings

Lists sprinkler temperature classifications, nominal temperature ratings, and maximum ambient temperatures.

Technical Specification

Provides key technical data including K-factor, thread size, orifice size, and pressure ratings.

SHIELD Upright, Pendent & Recessed Pendent Sprinkler Data

Part List (SD1015, SD1010, SD1030, SD1032)

Illustrates and lists the components of the SD1015, SD1010, SD1030, and SD1032 sprinkler models.

Discharge Curve

Presents a graph showing water discharge versus pressure for K=5.6 and K=8.0 sprinklers.

SHIELD Upright, Pendent & Recessed Pendent Sprinkler Installation & Safety

Warnings

Highlights critical safety precautions and responsibilities for sprinkler installation and maintenance.

Wrench Description

Describes the specialized wrench required for proper sprinkler installation and to prevent damage.

Installation Guide

Outlines general installation requirements, compliance with standards, and system preparation.

Installation Sequence

Provides step-by-step instructions for correctly installing the sprinkler units.

Cautionary Notes

Offers important advice regarding over-tightening and protecting the sprinkler bulb during handling.

Maintenance Procedures

Details requirements for maintaining sprinkler integrity, avoiding alterations, and visual inspections.

Additional Installation Notes

Provides specific instructions for installing recessed escutcheon plates.

SHIELD Upright, Pendent & Recessed Pendent Sprinkler Distribution Patterns

K5.6 Pendent Sprinkler Trajectory

Illustrates water distribution trajectory for K5.6 Pendent sprinklers at various pressures.

K5.6 Upright Sprinkler Trajectory

Illustrates water distribution trajectory for K5.6 Upright sprinklers at various pressures.

SHIELD Upright, Pendent & Recessed Pendent Sprinkler Dimensions

Upright Sprinkler Dimensions

Provides detailed measurements for the Upright Sprinkler model.

Pendent Sprinkler Dimensions

Provides detailed measurements for the Pendent Sprinkler model.

Recessed Pendent Sprinkler Dimensions

Provides detailed measurements for the Recessed Pendent Sprinkler, including extension and recess.

SHIELD Horizontal Sidewall Sprinkler Head

Description

Details the design, features, and materials of the SHIELD Horizontal Sidewall sprinkler.

Sprinkler Operation

Explains the heat-responsive glass bulb mechanism and water discharge process.

Maximum Coverage

Specifies coverage areas for Light and Ordinary Hazard classifications per NFPA 13.

Ratings

Lists temperature classifications, nominal ratings, and maximum ambient temperatures.

Technical Specification

Provides key technical data including K-factor, thread size, and pressure ratings.

SHIELD Horizontal Sidewall Sprinkler Data

Part List (SD1133, SD1121)

Illustrates and lists the components of the SD1133 and SD1121 sprinkler models.

Discharge Curve

Presents a graph showing water discharge versus pressure for K=5.6 and K=8.0 sprinklers.

SHIELD Horizontal Sidewall Sprinkler Installation & Safety

Warnings

Highlights critical safety precautions and responsibilities for installation and maintenance.

Wrench Description

Describes the specialized wrench for proper installation and to prevent damage.

Installation Guide

Outlines installation requirements, compliance with standards, and system preparation.

Additional Installation Notes

Provides specific instructions for installing recessed escutcheon plates.

Installation Sequence

Provides step-by-step instructions for correctly installing horizontal sidewall sprinklers.

Cautionary Notes

Offers advice on over-tightening and protecting the sprinkler bulb during handling.

Maintenance Procedures

Details maintenance requirements, avoiding alterations, and visual inspections.

SHIELD Horizontal Sidewall Sprinkler Distribution Patterns

Trajectory Patterns

Illustrates water distribution trajectory for horizontal sidewall sprinklers at various pressures.

Plan View Patterns

Shows water distribution patterns in a plan view for horizontal sidewall sprinklers.

SHIELD Horizontal Sidewall Sprinkler Dimensions

SHIELD Vertical Sidewall Sprinklers

Description

Details the design, features, and materials of the SHIELD Vertical Sidewall sprinkler.

Sprinkler Operation

Explains the heat-responsive glass bulb mechanism and water discharge process.

Maximum Coverage

Specifies coverage areas for Light and Ordinary Hazard classifications per NFPA 13.

Ratings

Lists temperature classifications, nominal ratings, and maximum ambient temperatures.

Technical Specification

Provides key technical data including K-factor, thread size, and pressure ratings.

SHIELD Vertical Sidewall Sprinkler Data

Part List (SD2133, SD2121)

Illustrates and lists the components of the SD2133 and SD2121 sprinkler models.

Discharge Curve

Presents a graph showing water discharge versus pressure for K=5.6 and K=8.0 sprinklers.

SHIELD Vertical Sidewall Sprinkler Installation & Safety

Warnings

Highlights critical safety precautions and responsibilities for installation and maintenance.

Wrench Description

Describes the specialized wrench for proper installation and to prevent damage.

Installation Guide

Outlines installation requirements, compliance with standards, and system preparation.

Additional Installation Notes

Provides specific instructions for installing recessed escutcheon plates.

Installation Sequence

Provides step-by-step instructions for correctly installing vertical sidewall sprinklers.

Cautionary Notes

Offers advice on over-tightening and protecting the sprinkler bulb during handling.

Maintenance Procedures

Details maintenance requirements, avoiding alterations, and visual inspections.

SHIELD Vertical Sidewall Sprinkler Distribution Patterns

Trajectory Patterns

Illustrates water distribution trajectory for vertical sidewall sprinklers at various pressures.

SHIELD Vertical Sidewall Sprinkler Dimensions

SHIELD Concealed Sprinklers

Description

Details the design, features, and materials of the SHIELD Concealed sprinkler.

Sprinkler Operation

Explains the heat-responsive glass bulb mechanism and water discharge process.

Maximum Coverage

Specifies coverage areas for Light and Ordinary Hazard classifications per NFPA 13.

Ratings

Lists temperature classifications, nominal ratings, and maximum ambient temperatures.

Technical Specification

Provides key technical data including K-factor, thread size, and pressure ratings.

SHIELD Concealed Sprinkler Data

Part List (SD1050, SD1055)

Illustrates and lists the components of the SD1050 and SD1055 sprinkler models.

Discharge Curve

Presents a graph showing water discharge versus pressure for K=5.6 and K=8.0 sprinklers.

SHIELD Concealed Sprinkler Installation & Safety

Warnings

Highlights critical safety precautions and responsibilities for installation and maintenance.

Wrench Description

Describes the specialized wrench for proper installation and to prevent damage.

Installation Guide

Outlines installation requirements, compliance with standards, and system preparation.

Additional Installation Notes

Provides specific instructions for installing the conceal cover plate.

Installation Sequence

Provides step-by-step instructions for correctly installing concealed sprinklers.

Cautionary Notes

Offers advice on over-tightening and protecting the sprinkler bulb and deflector.

Maintenance Procedures

Details maintenance requirements, avoiding alterations, and visual inspections.

SHIELD Concealed Sprinkler Distribution Patterns

K5.6 Pendent Sprinkler Trajectory

Illustrates water distribution trajectory for K5.6 Pendent sprinklers at various pressures.

SHIELD Concealed Sprinkler Dimensions

SHIELD Quick Response Upright & Pendent Sprinklers

Description

Details the design, features, and materials of the SHIELD Quick Response Upright & Pendent sprinklers.

Sprinkler Operation

Explains the heat-responsive glass bulb mechanism and water discharge process.

Maximum Coverage

Specifies coverage areas for Light and Ordinary Hazard classifications per NFPA 13.

Ratings

Lists temperature classifications, nominal ratings, and maximum ambient temperatures.

Technical Specification

Provides key technical data including K-factor, thread size, and pressure ratings.

SHIELD Quick Response Sprinkler Data

Part List (SD1020, SD1021)

Illustrates and lists the components of the SD1020 and SD1021 sprinkler models.

Discharge Curve

Presents a graph showing water discharge versus pressure for K=4.2 and K=6.0 sprinklers.

SHIELD Quick Response Sprinkler Distribution Patterns

K4.2 Pendent Sprinkler Trajectory

Illustrates water distribution trajectory for K4.2 Pendent sprinklers at various pressures.

K4.2 Upright Sprinkler Trajectory

Illustrates water distribution trajectory for K4.2 Upright sprinklers at various pressures.

SHIELD Quick Response Sprinkler Dimensions

Upright Sprinkler Dimensions

Provides detailed measurements for the Upright Sprinkler model.

Pendent Sprinkler Dimensions

Provides detailed measurements for the Pendent Sprinkler model.

Recessed Pendent Sprinkler Dimensions

Provides detailed measurements for the Recessed Pendent Sprinkler, including extension and recess.

SHIELD Conventional Sprinklers

Description

Details the design, features, and materials of the SHIELD Conventional sprinkler.

Sprinkler Operation

Explains the heat-responsive glass bulb mechanism and water discharge process.

Maximum Coverage

Specifies coverage areas for Light and Ordinary Hazard classifications per NFPA 13.

Ratings

Lists temperature classifications, nominal ratings, and maximum ambient temperatures.

Technical Specification

Provides key technical data including K-factor, thread size, and pressure ratings.

SHIELD Conventional Sprinkler Data

Part List (SD1025, SD1026)

Illustrates and lists the components of the SD1025 and SD1026 sprinkler models.

Discharge Curve

Presents a graph showing water discharge versus pressure for K=5.6 and K=8.0 sprinklers.

SHIELD Conventional Sprinkler Installation & Safety

Warnings

Highlights critical safety precautions and responsibilities for installation and maintenance.

Wrench Description

Describes the specialized wrench for proper installation and to prevent damage.

Installation Guide

Outlines installation requirements, compliance with standards, and system preparation.

Additional Installation Notes

Provides specific instructions for installing recessed escutcheon plates.

Installation Sequence

Provides step-by-step instructions for correctly installing conventional sprinklers.

Cautionary Notes

Offers advice on over-tightening and protecting the sprinkler bulb.

Maintenance Procedures

Details maintenance requirements, avoiding alterations, and visual inspections.

SHIELD Conventional Sprinkler Distribution Patterns

K5.6 Conventional Sprinkler Trajectory

Illustrates water distribution trajectory for K5.6 Conventional sprinklers at various pressures.

SHIELD Conventional Sprinkler Dimensions

Standard Conventional Sprinkler Dimensions

Provides detailed measurements for the standard conventional sprinkler.

Recessed Conventional Sprinkler Dimensions

Provides detailed measurements for the recessed conventional sprinkler.

SHIELD Sprinkler Accessories

Escutcheon Plates

Describes single-piece escutcheon plates for 1/2" and 3/4" sprinkler heads.

Recessed Escutcheon Plates

Describes adjustable, double-piece escutcheon plates for 1/2" and 3/4" sprinkler heads.

Hinged Escutcheon Plates for Pipe

Describes hinged escutcheon plates for pipes in various sizes from 1/2" to 6".

Sprinkler Guards

Describes nickel or chrome plated guards suitable for 1/2" and 3/4" sprinkler heads.

Sprinkler Cabinets

Describes red painted steel cabinets available for 6, 12, and 24 sprinkler heads.

Shield SD1010 Specifications