DESCRIPTION
The SHIELD Sprinklers, SD1010, SD1015, SD1030, SD1032
(Glass Bulb Type), Standard Orice, Upright, Pendent and
Recessed Pendent type, design incorporates state-of-the-art,
heat responsive, frangible glass bulb design (standard or quick
response)forprompt,preciseoperation.
The die cast frame is more streamlined and attractive than
traditionalsandcastframes.Itiscastwithahex-shapedwrench
boss to allow easy tightening from many angles, reducing assembly
effort. This sprinkler is available in various temperature ratings
and nishes to meet many design requirements. The recessed
pendent should be utilized with a recessed escutcheon which
provides up
”of adjustments. AllSprinklersaremanufactured
usingthetimeprovenBellevillesealusedexclusivelybyallmajor
manufacturestoensurelonglifeandsafeoperation.
SPRINKLER OPERATION
Theoperatingmechanismisafrangibleglassbulbwhichcontains
aheatresponsive liquid. Duringare, theambienttemperature
risescausingtheliquidinthebulbtoexpand.Whentheambient
temperature reaches the rated temperature of the sprinkler, the
bulbshatters. Asaresult, thewaterwayis clearedofallsealing
partsandwaterisdischargedtowardsthedeector.Thedeector
is designed to distribute the water in a pattern that is most
effectiveincontrollingthere.
MAXIMUM COVERAGE
Standard spray coverage is up to: Light Hazard = 225 square
feet(20.9sq.m);OrdinaryHazard=130squarefeet(12.1sq.m)per
NFPA13.
TECHNICAL SPECIFICATION
RATINGS
SPRINKLER HEAD
Upright, Pendent & Recessed Pendent Sprinklers
SprinklerIdentication
Number
Standard SD1015, SD1010
(bulb5mm),QuickResponse
SD1030,SD1032(bulb3mm)
Style Upright Sprinkler SD1015,
SD1032, Pendent &
Recessed Pendent
SD1010, SD1030
K Factor 5.6gpm/psi
½
.(80lpm/bar
½
)
ResponseTimeIndex
(RTI)
Standard 50
Quick Response 30
NominalThreadSize
½
”NPT(15mm)
OrceSize 13mm
Max.WorkingPressure 175PSI(1200kPa)
FactoryHydrostaticTest 100%@500PSI(3450kPa)
Min.OperationPressure 7PSI(48kPa)
SprinklerTemperature
Classication
Norminal Sprinkler
TemperatureRating
N.F.P.AMaximumAmbient
(Ceiling)Temp.(Allowed)
Glass Bulb Color
Ordinary** 155ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
High* 286ºF/141ºC 225ºF/107ºC Blue
ExtraHigh* 360ºF/182ºC 300ºF/149ºC Mauve
Open* Open - No Bulb
*Non-Approved
**ULListedonly.