6
www.shieldglobal.com
MODEL: SD1010, SD1015, SD1030, SD1032
DESCRIPTION
The SHIELD Sprinklers, SD1010, SD1015, SD1030, SD1032
(Glass Bulb Type), Standard Orice, Upright, Pendent and
Recessed Pendent type, design incorporates state-of-the-art,
heat responsive, frangible glass bulb design (standard or quick
response) for prompt, precise operation.
The die cast frame is more streamlined and attractive than
traditional sand cast frames. It is cast with a hex-shaped wrench
boss to allow easy tightening from many angles, reducing assembly
effort. This sprinkler is available in various temperature ratings
and nishes to meet many design requirements. The recessed
pendent should be utilized with a recessed escutcheon which
provides up of adjustments. All Sprinklers are manufactured
using the time proven Belleville seal used exclusively by all major
manufactures to ensure long life and safe operation.
SPRINKLER OPERATION
The operating mechanism is a frangible glass bulb which contains
a heat responsive liquid. During a re, the ambient temperature
rises causing the liquid in the bulb to expand. When the ambient
temperature reaches the rated temperature of the sprinkler, the
bulb shatters. As a result, the waterway is cleared of all sealing
parts and water is discharged towards the deector. The deector
is designed to distribute the water in a pattern that is most
effective in controlling the re.
MAXIMUM COVERAGE
Standard spray coverage is up to: Light Hazard = 225 square
feet(20.9 sq.m); Ordinary Hazard = 130 square feet(12.1 sq.m) per
NFPA 13.
TECHNICAL SPECIFICATION
RATINGS
SPRINKLER HEAD
Upright, Pendent & Recessed Pendent Sprinklers
Sprinkler Identication
Number
Standard SD1015, SD1010
(bulb 5mm), Quick Response
SD1030, SD1032 (bulb 3mm)
Style Upright Sprinkler SD1015,
SD1032, Pendent &
Recessed Pendent
SD1010, SD1030
K Factor 5.6gpm/psi
½
. (80lpm/bar
½
)
Response Time Index
(RTI)
Standard 50
Quick Response 30
Nominal Thread Size ½”NPT(15mm)
Orce Size 13mm
Max. Working Pressure 175PSI(1200kPa)
Factory Hydrostatic Test 100%@500PSI(3450 kPa)
Min. Operation Pressure 7 PSI(48 kPa)
Sprinkler Temperature
Classication
Norminal Sprinkler
Temperature Rating
N.F.P.A Maximum Ambient
(Ceiling) Temp.(Allowed)
Glass Bulb Color
Ordinary** 155ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
High* 286ºF/141ºC 225ºF/107ºC Blue
Extra High* 360ºF/182ºC 300ºF/149ºC Mauve
Open* Open - No Bulb
* Non-Approved
**UL Listed only.