7
77
7-
--
-2. Cause and Treatment of Error Display
2. Cause and Treatment of Error Display2. Cause and Treatment of Error Display
2. Cause and Treatment of Error Display
(1) Abnormality Display of Measurement Input
Error display Contents Cause Treatment
(HHHH)
Scale over in upper limit 1.wire breaking of thermocouple input
2.wire breaking of resistance bulb input A
3.when input exceeds upper limit of measuring range by 10%
1.wire breaking check of thermocouple input wiring,
replacement of thermocouple
2.check of resistance bulbA wiring, replacement of
resistance bulb
3.check of input voltage value and current value, input
transmitter and specification (matching of incoming
signal and meter specification)
1.when input exceeds lower limit of measuring range by 10%
2.wire breaking of resistance bulb input B*
1.polarity of input is everse, check of wiring and an input
transmitter
2.check of resistance bulb B wiring,replacement of
resistance bulb
(LLLL)
Scale over in lower limit
*B: Wiring of MAC3A, 3B's terminal No.11, Wiring of MAC 3D's terminal No.5
1.wire breaking of b* 1.check of resistance bulb wiring
*b: Wiring of MAC 3A, 3B's terminal No.12,wiring of MAC 3D's terminal No.6
(B---)
Breaking of resistance bulb input
2.multiple wire breaking combinations in Abb
(A and B, A and b, B and b, all of ABB)
2.replacement of resistance bulb
(CJHH)
Cold junction (CJ) temperature of thermocouple
input is scale over in lower limit side
When ambient temperature of meter becomes less
than -20℃
1.make Ambient temperature of meter within use environment
condition temperature
2. Check the meter when ambient temperature is not less than
-20℃
8. Specification
8. Specification8. Specification
8. Specification
Display
Display method Digital display: MAC3A (96 x 96 size) PV red 7 segment LED 4 figure (height of character about 20mm)
SV green 7 segment LED 4 figure (character quantity about 13mm)
MAC3B(48x96 size) PV red 7 segment LED 4 figure (height of character about 12mm)
SV green 7 segment LED 4 figures (height of character about 9 mm)
MAC3C(72 x72 size) PV red 7 segment LED 4 figure (height of character about 16mm)
SV green 7 segment LED 4 figures (height of character about 16 mm)
MAC3D (48x48 size) PV red 7 segment LED 4 figure (height of character about 12mm)
SV green 7 segment LED 4 figures (height of character about 9mm)
Status display: RUN (green), PRG (green), AT (green), OUT 1(green)
EV1 (yellow), EV2 (yellow), OUT2 /EV3 (yellow)
Display accuracy : ±(0.25%FS+1digit)CJ errors not included, B thermo couple below 400℃ is not guaranteed.
Display accuracy during EMC examination is ±5%FS.
Accuracy maintenance range : 23±5℃
Display range : -10%-110% of measuring range, but Pt100's -200~600℃ is -240~680℃
Display resolution : Changes with measuring range and scaling.
Input scaling : Possible at the time of voltage input and current input -1999-9999 (spang 10 – 10000 count, decimal point position
no decimal point 0.1, 0.01, 0.001)
Setting
Setting system : By five front keys ( , , ).
SVSetting range : Same with measuring range
Setting lock : Communication and key seting (three levels), DI (one level)
Operations Level Lock Content
OFF No lock
1 Execution SV and a manual numerical change are possible. And change of a keylock level is possible.
2 Possible to change numerical value manually and keylock level.
Communication
&
Key setting
3 Possible to change keylock level.
4 Only change of a keylock is possible It can be locked key
DI Setting Super Key Lock (Shift between screens prohibited. Fixed only to the basic screen.)
*Regardless of the setting lock by communication & key setting, the key is always effective.
However, even key is not received when super keylock by DI is performed.
SV setting limiter :Same with measuring range ( lower limit < upper limit )
Unit setting :Settable at the time of sensor input ℃,°F
Input
Multi input
Thermocouple :500Ω or more, external resistance tolerance level 100Ωor less input resistance
Influence of lead-wire :1.2μV/10Ω
Burnout :Standard equipment (Up Scale only)
Measuring range :Item 5-5. Refer to measuring range code table.
Compensation accuracy
of reference junction :±1℃ (ambient temperature 18-28℃) At the time of vertical plural proximity attachment ±2℃
±2℃(ambient temperature 0-50℃) At the time of vertical plural proximity attachment ±3℃