Several minutes after power-on, accuracy is not guaranteed. Reaches the accuracy level within 5 minutes after power-on.
Tracking of a reference
junction :Below the ambient temperature of 0.5 / min, compensation accuracy of reference junction ±1℃
Resistance bulb stipulated
current resistance bulb :Approx. 0.25mA
Lead wire resistance
tolerance level :5Ω or less per wire (Resistance of three lines should be equal)
Influence of lead-wire
resistance 5Ω or less per wire 0.2%FS
10Ω or less per wire 0.5%FS
20Ω or less per wire 1.0%FS
Measuring range :Item 5-5. Refer to measuring range code table.
Voltage (mV) Input resistor 500kΩ or more
Input voltage range :Item 5-5. Refer to measuring range code table.
Voltage input (V) Input resistor:500kΩ or more
Input voltage range :Item 5-5. Refer to measuring range code table.
Current input (mA) reception
Resistance :250Ω (built-in)
Input range :Item 5-5. Refer to measuring range code table.
Sampling period 0.25 second
PV filter 0 - 9999 second
PV offset compensation ±500 unit
PV gain correction ±5.00%PV filter
Control
Control system PID control with an auto tuning function or ON-OFF operation
Proportional band (P) :OFF and 0.1 - 999.9% of measuring range (ON-OFF operation by OFF setting)
ON-OFF Differential-gap (DF) :1 - 999 unit
Integration Time (I) :OFF, 1- 6000 seconds (PD operation by OFF setting) If both I and D are OFF, P operation.
Manual Reset (MR) :±50.0% (effective when set as I = OFF)
Output 2 dead band -1999 - 5000 unit
Output limiter (OL, OH) :0.0 - 100.0% (OL<OH) (set resolution 0.1)
Soft start :OFF, 0.5 - 120.0 seconds (set resolution 0.5)
Proportional period :0.5 - 120.0 seconds (set resolution 0.5)
Control output characteristic Output 1, output 2. Possible to choose either RA (heating) or DA (cooling).
Manual output :0.0 - 100.0% (set resolution 0.1)
Each parameter,( P, I, D, DF, MR, OL, and OH) of Outputs 1 and Outputs 2, Flex PID belongs to 1~3 categories.
Control output 1
Contact :normal open (1a) 240V AC 2A (resistance load)
Voltage pulse (SSR drive) :12V DC+1.0--1.5V MAX20mA
Current :4 - 20mA DC load resistance 500Ω or less Display accuracyaccuracy±1% (accuracy maintenance range 23℃±5℃)
Load regulation ±0.2%, resolution approx. 1/12000
Control out put 2 (option) Control out put 2 is exclusive option of event 3 and DI4.
Contact :normal open (1a) 240V AC 2A (resistance load)
Voltage pulse (SSR drive) :12V DC+1.0--1.5V MAX20mA
Current :4 - 20mA DC load resistance 500Ω or less ,display accuracy±1% (accuracy maintenance range 23℃±5℃ )
Load regulation ±0.2%, resolution approx. 1/200
Program function (option)(40step fuinction add from Ver 1.3*)
Number of pattern :Choosen from pattern 1,2,4 Add from Ver 1.3*
Number of steps :Maximum 40steps When choose pattenn 1,20steps of each steps when choose pattern 2,10steps of each steps when choose pattern 4.
PID selection :Each output has three kinds. PID1, PID2, and PID3.
Time setting :0 minute 0 second~99 minutes 59 seconds or 0 hour 0 minute~99 hours 59 minutes or 0.0 - 999.9 hours ,and (infinity)
Time setup resolution :1 second or 1 minute or 0.1 hour
Time accuracy :± (Setup time × 0.005 +0.25 second)
In a step Setting parameter :SV, time, PID№
Number of repeats :1 - 9999 times, and
Time signal Possible to allot to Event (1 second for changeover, 3 seconds for patter end, 3 seconds for program end)
PV start function :With
Guarantee soak function :With Off or 1-2000unit(add from Ver 1. 2*)
Time hold facility :Possible at front key, DI allotment, or communication
Step skip Possible at front key, DI allotment, or communication
Power failure compensation :without (setting contents being held.However, elapsed time, execution step, and number of execution are reset.)