Event 1・2 (option) :2 sets
Output rating :Contact Normal open (1a) 240V AC 2A (resistance load) EV1・EV2 and common
Kind of event :Refer to following table.
Function Character Note
No allotment
Upper limit absolute value Alarm
Lower limit absolute value alarm
Scale over alarm HHHH, LLLL, B---- Operates, when displayed.
Upper limit deviation value Alarm
Lower limit deviation value alarm
Within deviation alarm
Without deviation alarm
RUN signal Operates during PROG and FIX in operation.
Control loop alarm
(Heater breaking / loop)
When contact/voltage pulse output is ON Breaking alarm, when it is below EV set.
When contact/voltage pulse output is OFF Loop alarm, when it is more than EV set.
Step signal Operate for 1 second at the time of step switchover
Pattern end signal Operate for 3 seconds at the time of pattern end
Program end signal For 3 seconds at the time of program end
Hold signal Operates during time hold.
Program signal Operates by program selection
Upslope signal Operates when the inclination of program control rises (including Hold status)
Downslope signal Operates when the inclination of program control descends (including Hold status)
Guarantee signal Operates when approaches the targeted value exceeding the EV value.
Setting range :Upper limit absolute value alarm, Lower limit absolute value alarm within measuring range
Upper limit deviation alarm, Lower limit deviation alarm -1999 - 2000 unit
Within deviation alarm, without deviation alarm 0 – 2000unit
Control loop alarm 0.0-50.0A
Standby operation :OFF No standby operation
1 Only at the Time of Power-on, standby operation
2 At the Time of power switch on, each alarm operating point is changed, deviation alarm's execution SV is changed,
and RUN/STBY (RST) is switched over standby operation, at the time of AUTO/MAN switchover
Latching :Alarm operation maintenance function(Release is done by key operation, DI, or power OFF.
In the case of release by DI and power OFF, all alarms are called off simultaneously)
Differential gap : 1 - 999 unit
Output characteristic : Choose from normal open (NO) or normal closing (NC).
If NC is chosen and power is turned on, relay becomes ON about 1.8 seconds and becomes OFF at event power range.
Event3 (Option) : Event3 is exclusive selection option of control out put 2 and DI4.
: Item and contents are same with event 1 and 2.
DI 1-2-3 (option) : Set of 3 In MAC 3D, exclusive selection option with CT input .
Input rating : 5V DC 0.5mA
Allotment function : Refer to following table.
DI
character
Operation type Input
detection