Input minimum retention time : 0.25 second
Input of operation : Non-voltage contact or open collector
DI4 (option) : DI4 is exclusive selection option with control output 2, Event3
Number of input : One
: Item and contents are same with DI 1, DI 2 and DI 3.
Communication function(option) :Output and an exclusive selection option for MAC 3D.
Read attached communication instructions manual that detailed about communication function.
Communicative type : EIA standard RS-485
Communication system : Two-wire system half duplex multi-drops (bus) system
Synchro system : Asynchronous system
Communication distance : Maximum 500m (dependson conditions)
Communication Speed : 1200, 2400, 4800, 9600, 19200 or 38400bps
Data format : Start 1bit, Stop 1 2 bits, Data length 7 or 8 bits, Parity without, odd number, even number
Master function : Chooses from SV, OUT1, OUT2 (1:n number of slaves maximum 31)
※ When MAC3 is a master, slave address range must be continuation.
※ When MAC3 is a master, bus connection with other host PCs is not allowed.
※ Input range of master machine and slave machine should be equal,at the time of cascade control
Slave address : 1-255
Parameter preservation mode: Choose from RAM, MIX and EEP mode.
Error detection : None, Choose from ADD, complement of ADD +2, exclusive OR, CRC-16 and LRC
Flow control : none
Delay : 1 - 500ms (resolution 1ms)
Communication code : ASCII code or binary code
Protocol : SHIMAX Standard or MODBUS ACII, MODBUS RTU protocol
Termination resistance : 120Ω (external connection)
Number of connection : Maximum 32 sets (depends on conditions, host is included)
Analog output(AO) : In MAC 3D, exclusive selection option with communication function
Output kind : Choose from PV, SV, OUT1, OUT2, CT1, and CT2.
Output rating : 4-20mA DC 300Ω or less, Display accuracy ±0.3% (accuracy maintenance range 23℃±5℃ )
Load regulation±0.05%, Resolution approx 1/50,000
Scaling function : with (range depends on output type) analog output lower limit value < analog output upper limit value
Output limiter : 0.0 - 100.0% (reverse setting is possible)
CT1・CT2 input : In MAC 3D, exclusive selection option with DI・D2・D3
Detection method : Current judging system by CT sensor
Detection range : 0.0-55.0A
Sampling period : 125ms
Detection accuracy : ±5%FS
Detection delay time : 0.5 - 30.0 seconds
Alarm output : Assigned to event
Detection Objects : Assigned to OUT1, OUT2, EV1, EV2, and EV3.
Alarm operating point
setting range : 0.0-50.0A
Recommended CT sensors : Products of U_RD co., CTL-6-L ,CTL-6-V, CTL-6-P-H, CTL-6-S-H, CTL-12L-8
General specification
General specificationGeneral specification
General specification
Data save : By nonvolatile memory (EEPROM)
Temporary dead time
: no influence within 0.02 second 100% dip
Use environmental condition : Temperature: -10~55 ℃
Humidity : Below 90%RH (no dew condensation)
Hight : Altitude of 2000m or less
Category : Ⅱ
Contamination degree : 2
Storage temperature Conditions : -20~65 ℃
Supply voltage : 90-264V AC 50/60Hz or 21.6-26.4V AC (50/60Hz)/DC
Power consumption : 90-264V AC maximum 9VA 21.6-26.4V AC maximum 6 VA 21.6-26.4V DC maximum 4W
Applicable standard Safety : IEC1010-1 and EN61010-1:2001
EMC : EN61326-1:1997+Amendment1:1998+Amendment2:2001
(EMI: ClassA, EMS: AnnexA)
EN61000-3-2:2000 EN61000-3-3:1995+Amendment 1:2001
IEC60529-1989+Amendment1: 1999
Oscillation : IEC60068-2-6/1995P
9Insulated class : Class I apparatus
Input noise removal ratio : Normal 50dB or higher
Impulse-proof noise : Power-source Normal 100ns/1μs±1500V
Insulation resistance : Between input/output terminal and power supply terminal 500V DC 20Ω or higher
: Between analog output or communication and other input/output terminals 500V DC 20Ω or higher
Withstand voltage : Between input/output terminal and power supply terminal 1500V AC 1 minute or 1800V AC 1 second