Digital Controller
MAC6A/
MAP6A
Instruction manual
Please ensure that this manual is given to the final user of this product.
MAP6F-1EE March 2017
Thank you for purchasing SHIMAX products.
Please check that the delivered Item is the item you ordered. Read this instruction manual
thoroughly and understand its contents before using this product.

Questions and Answers

  • E
    elizabethadamsAug 12, 2025
    What to do if Shimax MAC6A Controller shows scale over in upper limit?
    • A
      agarciaAug 13, 2025
      If the Shimax Controller displays a scale over in the upper limit, it could be due to a few reasons: 1. There might be a wire break in the thermocouple input. Check the thermocouple input wiring and consider replacing the thermocouple. 2. There might be a wire break in the resistance bulb input A. Check the wiring of resistance bulb A and consider replacing it. 3. The input might be exceeding the upper limit of the measuring range by 10%. Verify the input voltage and current values, and ensure that the input transmitter and controller specifications match.
  • J
    Jennifer FloresAug 16, 2025
    Why did the display disappear and Shimax MAC6A does not operate?
    • S
      simmonscrystalAug 16, 2025
      If the Shimax Controller's display has disappeared and the device isn't operating, the cause could be that power isn't being supplied or there is an abnormality with the instrument itself. To resolve this, check the power supply, including the terminal voltage, switch, fuse, and wiring.
  • E
    Elizabeth GuzmanAug 19, 2025
    What to do if Shimax Controller shows scale over in lower limit?
    • S
      Samantha PageAug 19, 2025
      If the Shimax Controller shows a scale over in the lower limit, it could be due to a couple of reasons: 1. The input might be exceeding the lower limit of the measuring range by 10%. In this case, check the polarity of the input, the wiring, and the input transmitter. 2. There might be a wire break in the resistance bulb input B. Check the wiring of resistance bulb B and consider replacing the resistance bulb.
  • T
    Thomas OliverAug 23, 2025
    How to troubleshoot abnormal PV display on Shimax MAC6A Controller?
    • D
      Destiny ThompsonAug 23, 2025
      If the PV display on your Shimax Controller is not normal, it may be due to a mismatch between the instrument and the input, or a fault in the wiring. To address this, verify the type code and specifications, and carefully check the wiring.
  • L
    leeshawnAug 27, 2025
    What to do if key operation is impossible on Shimax Controller?
    • S
      Sherry RowlandAug 27, 2025
      If key operation is impossible on your Shimax Controller, it could be due to the key being locked or an abnormality with the instrument. Try releasing the keylock. If that doesn't work, check the instrument for any issues, and consider repairing or exchanging it.
  • T
    Tyler ZimmermanAug 31, 2025
    Why Shimax MAC6A shows cold junction temperature scale over in upper limit?
    • J
      Jerry StricklandAug 31, 2025
      If the cold junction (CJ) temperature of the thermocouple input is scaling over on the upper limit side in your Shimax Controller, it may be because the ambient temperature of the meter exceeds 80 degrees Celsius. Consider the following: 1. Ensure the meter's ambient temperature is within the specified use environment conditions. 2. Check the meter when the ambient temperature is not over 80 degrees Celsius.
  • J
    jonesjessicaSep 4, 2025
    Why Shimax MAC6A shows cold junction temperature scale over in lower limit?
    • C
      Christian AlvaradoSep 4, 2025
      If the cold junction (CJ) temperature of the thermocouple input is scaling over on the lower limit side in your Shimax Controller, it may be because the ambient temperature of the meter is less than -20 degrees Celsius. Consider the following: 1. Ensure the meter's ambient temperature is within the specified use environment conditions. 2. Check the meter when the ambient temperature is not less than -20 degrees Celsius.
  • B
    Brandon SmithSep 7, 2025
    What causes breaking of resistance bulb input in Shimax Controller?
    • E
      Erin Duncan DDSSep 8, 2025
      If experiencing breaking of resistance bulb input on your Shimax Controller, this could be due to: 1. A wire break. Check the resistance bulb wiring. 2. Multiple wire breaking combinations in ABb (A and B, A and b, B and b, all of ABb). Replace the resistance bulb.