49
Sampling period time setting screen
Initial Value : 167
Setting range : 50, 167, 250, 500ms
Sampling period time can be set according to each application.
Being initialized when sampling period is changed.
Mode1 lead screen
6-6-2. Mode2 PV setting screen
Mode 2 setting screen lead screen.
PV offset correction (PV bias) setting screen
Initial Value : 0.0
Setting range : digit
Used for correction of input errors such as sensor.
If offset correction is performed, control is also performed with the corrected value
PV gain correction setting screen
Initial value : 0.000
Setting range: ±.000%
Maximum input value is corrected within limit of ±5.00 % of measuring range. If
corrected, inclination of span changes in straight line which connects zero point
and correction maximum value.