Freon shortage
Case-10
R410
Lo Hi
Factor
Cooling capacity downs by the freon shortage.
Tube Extending and freon adding.
Troubles &
Causes
Defect Details
Guidelines
Ensure to add freon after extending tubings.(For
a simple check of proper freon quantity, com
pare the in-and-out air temperature after 15 m in
from com pressor's running.)
Air in
Detect the gas leakages before insulation
tubing(confirm new welded points).
1. Not adding freon for extended tubings. 2. Gas leakage on welded points for extending
tubings.
< Temp. diff. >
-Cooling: 8deg
-Heating: 14deg
Air out
Air Conditioner Service Manual