5 Mounting
5.1 Safety
DANGER
H
azard due to unexpected starting of the machine
Hazard due to electrical voltage
b
Make sure that the outputs of the safety relay have no effect on the machine dur‐
ing mounting and electrical installation.
b
Make sure that the safety relay and the connected components are isolated from
all voltage sources during mounting and electrical installation of the device and
during mounting/dismantling of the front connector.
NOTICE
Enclosure rating IP20 only applies if the front connector is mounted.
5.2 Mounting procedure
Prerequisites
Mount
ing is done in accordance with EN 50274 and electrical installation in
accordance with IEC 60204-1 in the control cabinet with enclosure rating IP54.
Mounting must be done on a non-flammable base.
Mounting is done on a 35 mm mounting rail (IEC 60715).
The mounting rail is connected to the functional earth.
The module is installed in a vertical orientation (on a horizontal mounting rail).
There is at least 50 mm of space for air circulation above and below the module.
There is at least 25 mm of space in front of the module (front side). More space
may be needed depending on the connections.
Approach
Click
Figure 5: Mounting
b
A
ttach module to mounting rail.
MOUNTING 5
8023925/2019-10-11 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy OSSD3