Table 10: Electrical data - application diagnostic output (Y1, Y2)
Type of output Push-pull semiconductor output, short-circuit
pr
otected
Output voltage HIGH: (U
V
– 3 V
) … U
V
Output voltage LOW: 0 V … 3 V
Input current (NPN) ≤ 15 mA
Output current (PNP) ≤ 120 mA
Table 11: Electrical data - enabling current paths (13, 14, 23, 24, 33, 34)
Response time 12 ms
Minimum switch-off time
1)
100 ms
Number of enabling current paths (normally
open, s
afe)
3
Contact type Positively guided
Contact material Silver alloy, gold flash plated
Switching voltage
At altitudes below 2,000 m above sea level 10 V DC … 250 V DC
10 V A
C … 250 V AC
At altitudes 2,000 m above sea level …
4,000 m abo
ve sea level
10 V DC … 150 V DC
10 V AC … 150 V AC
Switching current 10 mA … 6 A, see
figure 10, page 27, see
figure 11, page 28
Sum current ≤ 12 A
Utilization category AC-15: 250 V, 5 A (IEC 60947-5-1)
DC
-13 (0.1 Hz): 24 V, 4 A (IEC 60947-5-1)
DC switching capacity 0.1 W … 200 W, see
figure 10, page 27
AC switching capacity 0.1 VA … 1,500 VA
Switching frequency ≤ 1 Hz
Mechanical service life 10 × 10
6
s
witching operations
Contact fuse with safety fuse gG or circuit
breaker C
6 A
Max. short-circuit protection ≤ 400 A
Rated insulation voltage
At altitudes up to 2,000 m above sea level 250 V AC
At altitudes up to 2,000 m above sea level …
4,000 m abo
ve sea level
150 V AC
Overvoltage category III
Contamination rating 2
Rated impulse withstand voltage U
im
p
6 kV
1)
Time the enabling current paths of the safety relay remain open before closing again.
2)
Applies to devices with version ≥ V1.10.0 in the “HW” type label entry.
W
ith devices with smaller version numbers or without the “HW” type label entry: Response time ≤ 12 ms;
response time with simultaneous dual-channel switch-off = 10 ms.
Table 12: Ambient data
Enclosure rating IP20 (IEC 60529)
Ambient operating temperature
10 TECHNICAL DATA
26
O P E R A T I N G I N S T R U C T I O N S | ReLy OSSD3 8023925/2019-10-11 | SICK
Subject to change without notice