Siemens ST 80 · 2006
2/121
Operator Control and Monitoring Devices
Panels — 270 series
SIMATIC OP 270
2
Technical specifications
SIMATIC
OP 270
5,7“ Color
STN Display
SIMATIC
OP 270
10,4“ Color
STN Display
Display
Display type STN liquid
crystal display
(LCD)
STN liquid
crystal display
(LCD)
•Size
5.7" 10.4"
Resolution (W x H in pixels)
320 x 240 640 x 480
Colors
256 colors 256 colors
MTBF of background lighting
(at 25 °C)
approx. 40,000
hours
approx. 60,000
hours
Operating mode
Control elements Membrane
keyboard
Membrane
keyboard
Operating options
Key Key
Function keys, programmable
24 function
keys,
18 with LEDs
36 function
keys,
28 with LEDs
Membrane keyboard
Yes Yes
System keys
36 38
Numeric/alphanumeric input
Yes/Yes Yes/Yes
External mouse/keyboard/bar-
code reader
USB/USB/USB USB/USB/USB
Processor/HW
RISC 32 bits,
180 MHz
RISC 32 bits,
180 MHz
Operating systems
Windows CE Windows CE
Memory
Type Flash/RAM Flash/RAM
Usable memory for project data
2028 KB user
memory/with-
out additional
memory for
options
2028 KB user
memory/with-
out additional
memory for
options
Interfaces (some only as options)
Interfaces 2 x RS232,
1 x RS422,
1 x RS485
max. 12 Mbit/s
2 x RS232,
1 x RS422,
1 x RS485
max. 12 Mbit/s
CF card slot
1 x CF card slot 1 x CF card slot
USB (universal serial bus)
1 x USB 1 x USB
Supply voltage
Supply voltage 24 V DC 24 V DC
Permissible range
+18 to +30 V
DC
+18 to +30 V
DC
Rated current
0.6 A 0.6 A
•Output
15 W 15 W
UPS can be connected (serial)
Yes Yes
Backup battery
Optional 3.6 V Optional 3.6 V
Clock
Hardware
clock, battery-
backed and
synchronized
Hardware
clock, battery-
backed and
synchronized
SIMATIC
OP 270
5,7“ Color
STN Display
SIMATIC
OP 270
10,4“ Color
STN Display
Degree of protection
Front IP65,
NEMA 4,
NEMA 4x,
NEMA 12;
(when
mounted)
IP65,
NEMA 4,
NEMA 4x,
NEMA 12;
(when
mounted)
Rear
IP20 IP20
Certification
(some only as options)
CE, GL, ABS,
DNV, LRS, FM
Class I Div. 2,
UL, cULus,
EX zone 2/22,
C-TICK
CE, GL, ABS,
DNV, LRS, FM
Class I Div. 2,
UL, cULus,
EX zone 2/22,
C-TICK
Mechanical components/
dimensions
Front panel W x H (mm) 308 x 204 483 x 310
Mounting cutout/depth W x H x D
(mm)
282 x 178/
59 mm depth
of unit
436 x 295/
55 mm depth
of unit
•Weight
1 kg 6 kg
Ambient conditions
Max. relative humidity (in %) 90% 90%
Mounting position
Vertical Vertical
- Max. permissible angle of
inclination without external fan
+/- 35° +/- 35°
•Temperature
- Operation (vertical installation) 0 to +50 °C 0 to +50 °C
-Operation
(max. angle of inclination)
0 to +35 °C 0 to +35 °C
- Transportation and storage
-20 to +60 °C -20 to +60 °C
Expansions for operator-process
communication
(may only be an option)
DP direct LEDs
(LEDs as S7 output I/O)
F1...F8,
K1...K10
F1...F12,
K1...K16
DP direct keys
(buttons as input peripherals)
F1...F14,
K1...K104 byte
or coded
F1...F20,
K1...K165 byte
or coded
Peripherals/applications/options
•I/O Printer, bar-
code reader
Printer, bar-
code reader
Applications/options
(with ProTool)
ProAgent ProAgent
Configuring
Configuration tool ProTool ProTool
Configuration tool
WinCC flexible WinCC flexible
© Siemens AG 2007