KMS-0021
98
2022-02-10
If no RCU’s have Operator Control Panels fitted then set this to Disabled. If one or more sites
will have a Operator Control Panel fitted then set this to Enabled (the RCU will then auto-detect
if a panel is fitted at a particular site).
11.4.2 Operator Control Panel Ignore Remote Switch
This setting allows the RCU to be configured so that Operator Control panel controls such as
Trip/Close or change of protection mode will always be allowed irrespective of the position of
the Remote Control ON switch. Setting options are:
TRUE: The RCU will allow controls from the Operator Control Panel to be sent to the
irrespective of the position off the Remote Control ON switch.
FALSE: The RCU will disable all controls from the Operator Control Panel if the Remote
Control Switch is ON.
11.5 Protocol Settings
Refer to the relevant protocol manual for protocol setting option explanations. The protocol
manual addresses:
Radio power supply settings
Radio/Modem Serial interface settings
SCADA Operation Settings
Protocol Point Configuration
DNP3 Configuration