Description
26 9229 9860 176 0E
2013-08-22
Auxiliary switch S1
Breaking capacity
Fig. 33 Breaking capacity of the auxiliary switch 3SV92
Two versions of the auxiliary switch S1 are available for
delivery: with 6 or 12 NO/NC contacts each.
Rated insulation voltage: 250 V AC/DC
Insulation group: C as per VDE 0110
Continuous current: 10 A
Closing capacity: 50 A
Fig. 32 Auxiliary switch (68.)
AC 40 to 60 Hz DC
Operating voltage Operating current Operating voltage Operating current
U (V) I (A) U (V) I (A)
Ohmic load Inductive load
(T = 20 ms)
Up to 230 10
24 10 10
48 10 9
60 9 7
110 5 4
220 2.5 2