18
Siemens · 10/2014
General data
3WL Air Circuit Breakers
3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC
ETU27B Electronic Trip Unit
ETU45B Electronic Trip Unit
Application:
Classical building, motor and system protection with
time-selective coordination for up to 6300 A.
Properties:
The same as ETU25B but also
Connectable neutral conductor protection
Permanently integrated ground-fault protection. Calculation
of the ground-fault current through vectorial summation
current formation
Technical details, see the table "Functional overview of the
electronic trip system" under "Technical specifications"
NSE0_00956c
Rating Plug
N
OFF
OFF ON
ETU27B
Rotary switch for delay,
ground-fault protection
N-conductor protection
on/off
value, ground-fault protection
Rotary switch for setting
Rated current module
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Indicator: fault in
overcurrent release
Sealing ring
Test socket
Clear pushbutton
Indicator:
cause of release
Rotary switch for delay,
short-circuit release
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Rotary switch for setting
value, overload release
Rotary switch for setting
value, instantaneous
short-circuit release
Indicator: overcurrent
release activated
Indicator: overload alarm
Query pushbutton
Test pushbutton
Short-circuit protection
fixed setting
Application:
Low-cost all-round system for intelligent buildings and all
types of industrial applications – "CubicleBUS integrated"
Properties:
The same as ETU25B but also
Adjustable time-lag class for overload protection
Selectable characteristic for overload and short-time
delayed short-circuit range (current discrimination) for
more accurate discrimination adaptation to upstream
fuses and protective devices
Thermal image as restart protection for tripped motor
outgoing units
Connectable and adjustable neutral conductor protection
Modular ground-fault protection module with alarm and
tripping functions which can be adjusted separately
Communication interface, metering function Plus, optional
connection of external modules or for retrofitting
Storage of events and causes of tripping for specific fault
analysis
Extended protection functions possible with metering
function
Optional high-contrast display with viewing angle
adjustment option
The protection functions can be set by means of a rotary
coding switch or slide switch
Technical details, see the table "Functional overview of the
electronic trip system" under "Technical specifications"
=
12
g
NSE0_00957c
Rating Plug
OFF ON
1
1
1
1
1
S
I
ETU45B
t
/
t
42
t
/
t
2
gg
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Indicator: fault in
overcurrent release
Sealing ring
Test socket
Rotary switch for setting
value, overload release
Rotary switch for setting
value, instantaneous
short-circuit release
Overload alarm
Overcurrent release
activated
Clear pushbutton
Indicator: cause of release
Rotary switch for delay,
short-circuit release
Rated current module
Selector for
ground-fault protection
Rotary switch for delay,
ground-fault protection
N-conductor protection on/off
Scroll up
COMMUNICATION
EXPANDED
Indicators:
Rotary switch for setting
value, short-circuit
protection
Rotary switch for setting
value, ground-fault
protection
Rotary switch for setting
value, ground-fault alarm
Test pushbutton
Query pushbutton
Option: alphanumeric display
Scroll down
Thermal memory on/off
Setting value
N-conductor overload
Indicator: ground-fault tripped
Indicator: ground-fault alarm
Option: ground-fault module
Rotary switch for delay,
overload release
Transfer of overload
characteristic
© Siemens AG 2015