55
Siemens · 10/2014
3WL Air Circuit Breakers
3WL non-automatic air circuit breakers up to 4000 A (DC)
Project planning aids
Size I, up to 2000 A, fixed-mounted version, 3- and 4-pole
Blue lines: 4-pole version (on request)
$ Mounting space for removal of the arc chutes
% Arc quenching space, space for electrical auxiliary circuit connections
& Grooves (4 mm wide, 5 mm deep) for supporting phase partitions
in the system
( Auxiliary connector with SIGUT screw terminals
) Auxiliary connector with spring-type connections
* Dimension to inside surface of the closed cabinet door
+ Fixing points for mounting the circuit breaker in the system
, "Secure OFF" locking device
- Key operation
/ Terminal face
2 Space for electrical auxiliary circuit connections
6 Circuit breaker upper edge, only 690 V +20 % and 1000 V circuit breaker
7 Arc quenching space facing grounded or non-conductive surfaces, only
690 V +20 % and 1000 V circuit breaker
8 Arc quenching space facing grounded or non-conductive surfaces, only
circuit breakers with breaking capacity class C
Safety clearances to grounded parts and to live parts,
see page 41.
Standard version
Horizontal connection
Optional connection variants
Front connection (single)
Front connection (double hole)
according to DIN 43673
Vertical connection
General