EasyManua.ls Logo

Siemens 5-GMI-250 - Checks of the Primary Power Path

Siemens 5-GMI-250
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
&
Overhaul
Page
21
Introduction
Pliers
Light
Hammer
Drift
Pins
:
1
/
8
,
3
/
16
and
1
/
4
in
.
diameter
Periodic
inspections
and
maintenance
are
essential
to
ob
-
tain
safe
and
reliable
operation
of
the
GMI
circuit
breaker
,
When
the
circuit
breaker
is
infrequently
operated
(
less
than
20
times
per
week
)
,
and
is
located
in
a
clean
and
dry
indoor
location
,
annual
inspections
are
usually
satisfactory
.
When
the
circuit
breaker
is
operated
more
than
20
times
per
week
,
or
when
adverse
environmental
conditions
exist
,
more
fre
-
quent
inspections
may
be
necessary
.
This
part
of
the
manual
is
designed
to
provide
general
guidance
for
maintenance
.
It
will
supplement
,
not
replace
individual
maintenance
programs
based
upon
special
ex
-
perience
and
knowledge
of
specific
installations
and
their
actual
operating
conditions
.
Recommended
Annual
Inspections
Periodic
inspections
occurring
at
annual
,
or
more
frequent
,
intervals
should
include
all
the
tasks
shown
in
Table
1
.
Recommended
procedures
for
each
of
the
listed
tasks
are
provided
in
this
section
of
the
manual
.
Table
1
.
Annual
Inspection
/
Maintenance
Tasks
Checks
of
the
Primary
Power
Path
Checks
of
the
Interrupter
Operator
Mechanism
Electrical
Control
Checks
High
Potential
Test
Inspection
and
Cleaning
of
Breaker
Insulation
Functional
Tests
A
WARNING
»
Hazardous
voltages
and
high
speed
mechanical
parts
can
cause
death
or
severe
personal
injury
and
property
damage
.
For
a
quick
reference
to
these
tasks
see
Annual
Inspec
-
tion
Tasks
chart
at
the
end
of
this
section
.
Removal
from
Switchgear
Read
instruction
manual
,
observe
safety
instructions
and
limit
use
to
qualified
per
-
sonnel
.
Prior
to
performing
any
inspection
checks
or
tests
,
the
circuit
breaker
must
be
removed
from
the
switchgear
.
The
Instal
-
lation
and
Initial
Functional
Tests
section
describes
the
removal
procedure
in
detail
.
Principal
steps
are
repeated
here
for
information
and
guidance
,
but
without
the
details
of
the
preceding
section
.
1
.
The
first
step
in
the
annual
inspection
procedure
is
to
de
-
energize
the
circuit
breaker
.
Figure
39
shows
the
outer
door
of
a
standard
switchgear
cubicle
opened
for
access
to
the
operator
panel
of
the
circuit
breaker
.
Recommended
Hand
Tools
Type
GMI
breakers
use
both
standard
American
and
metric
fasteners
.
Metric
fasteners
are
used
for
the
GMI
vacuum
interrupters
.
American
fasteners
are
used
in
all
other
loca
-
tions
.
This
list
of
hand
tools
describes
those
normally
used
in
disassembly
and
re
-
assembly
procedures
.
Metric
(
Vacuum
Interrupter
,
Only
)
Deep
Sockets
:
18
and
24
mm
Torque
Wrench
,
0
-
150
Nm
(
0
-
100
Ib
-
ft
)
American
(
All
Other
Breaker
Locations
)
Socket
and
Open
-
end
Wrenches
:
5
/
16
,
3
/
8
,
7
/
16
,
1
/
2
,
9
/
16
,
and
3
/
4
inch
Hex
Keys
:
3
/
16
and
1
/
4
in
Screw
Drivers
:
0.032
x
1
/
4
in
wide
and
0.55
x
7
/
16
in
.
wide
Figure
40
illustrates
the
location
of
the
Trip
control
on
the
circuit
breaker
operator
panel
.
Depressing
the
Trip
pushbutton
opens
the
breaker
prior
to
removal
from
the
switchgear
.
The
second
step
in
the
removal
procedure
is
to
de
-
ener
-
gize
control
power
to
the
circuit
breaker
.
Open
the
control
power
disconnect
device
mounted
above
the
lower
breaker
or
below
the
upper
breaker
.
Review
Fig
-
ure
1
.
Rack
the
breaker
to
the
Disconnect
position
.
2
.
»
3
.
Courtesy of NationalSwitchgear.com

Other manuals for Siemens 5-GMI-250

Related product manuals