1
Alle Rechte vorbehalten. All rights reserved.
© Siemens AG 1998
Leistungsschalter 3WN6
AC Circuit-Breaker
Betriebsanleitung/
Operating Instructions
Bestell-Nr./
Order No.
: 3ZX1812-0WN60-0AN6 / 9239 9757 174 0F
Festeinbauschalter 3WN6, Baugröße I /
Fixed -mounted circuit-breaker 3WN6, size I

Other manuals for Siemens 3WN6

Questions and Answers

  • J
    Jacob MartinezJul 30, 2025
    What to do if Siemens Industrial Equipment breaker won't close electrically?
    • R
      robert97Jul 30, 2025
      If your Siemens Industrial Equipment breaker will not close electrically, but the ready-to-close indicator is OK, consider the following: * The operating voltage of the stored-energy activation solenoid might be incorrect or unavailable: Check or apply the correct voltage. * The circuit-breaker may be in the disconnected position in the guide frame: Crank the circuit-breaker into the test or connected position. * The auxiliary circuit plug may be taken out: Plug in the auxiliary circuit plug.
  • M
    Miss Hannah ColeAug 4, 2025
    Why can't I fit the crank for racking my Siemens Industrial Equipment?
    • B
      braunoliviaAug 4, 2025
      If you cannot fit the crank for racking on your Siemens Industrial Equipment, check the following: 1. Ensure the OFF push button is pressed: Press the OFF pushbutton and move the slide simultaneously to the right. 2. Verify the switchgear cabinet door is completely closed: Close the switchgear cabinet door. 3. Check for obstructions in the crank hole: Remove any padlocks that may be closing the crank hole.
  • T
    troyfrancisAug 9, 2025
    What to do if Siemens Industrial Equipment breaker is stuck in maintenance position?
    • D
      Dana SantiagoAug 9, 2025
      If the Siemens Industrial Equipment breaker cannot be moved from the maintenance position to the disconnected position, consider these causes: 1. The racing-in mechanism of the breaker is not in the disconnected position: Crank the mechanism into the disconnected position. 2. An attempt was made to fit a breaker with a different rated current in the guide frame: Only insert a circuit-breaker with the same rated current data as the guide frames. 3. The coding of the breaker and guide frame do not match: Only insert circuit-breaker with the same rated current data as the guide frames.
  • J
    Julie RiceAug 14, 2025
    Why can't I pull out the guide rails on my Siemens Industrial Equipment?
    • N
      Nathaniel HansenAug 14, 2025
      If the guide rails of your Siemens Industrial Equipment cannot be pulled out for fitting a circuit-breaker, it might be because the shutter is locked with one or two padlocks. Remove the padlocks to resolve this issue.
  • J
    Jessica KleinAug 20, 2025
    What causes resistance when cranking Siemens Industrial Equipment from disconnected to test?
    • L
      Linda WrightAug 20, 2025
      If you feel strong resistance immediately after leaving the disconnected position when cranking your Siemens Industrial Equipment from the disconnected into the test position, it may be because the breaker is not pushed right in, and the lateral latches are not yet engaged. Push the breaker as far as the stop into the disconnected position until the latches at the side engage.
  • A
    andrewwagnerOct 24, 2025
    How to fix Siemens Industrial Equipment breaker that won't close?
    • E
      Emily AndersonOct 25, 2025
      If the Siemens Industrial Equipment breaker cannot be closed mechanically or electrically, and the ready-to-close indicator is on, consider these potential causes: 1. The spring may not be charged: Charge the spring. 2. The undervoltage release may not be excited: Energize the undervoltage release. 3. The mechanical reclosing lock-out may be effective: Rectify the cause of overcurrent tripping and press RESET. 4. The electrical closing interlock may be effective: Shut off control voltage for interlocking. 5. The mechanical OFF push-button may be blocked off: Clear the pushbutton. 6. Lockout against closing with switchgear cabinet door open effective: Close switch gear cabinet door. 7. Mutual mechanical breaker interlocks effective: Open second breaker or crank into disconnected pos...

Summary

1. Aufbau des Leistungsschalters; Circuit-breaker design

3. Installation; Installation

Einbau; Installation

Details the mounting positions and procedures for installing the breaker.

Anschluß der Hauptstromleiter; Connecting the main conductors

Gesamtschaltplan; Overall circuit diagram

Schaltplan für Unterspannungsauslöser d.c.

Hinweise zum Überstomauslöser; Notes on the overcurrent release

Important notes and precautions regarding the overcurrent release.

Verzögerungszeit des Unterspannungsauslösers einstellen

Einstellung der Verzögerungszeit

Instructions for setting the delay time for the undervoltage release.

Abschließende Arbeiten und Schutzmaßnahmen

Schutzmaßnahmen; Protecting measures

Details on protective measures, including earthing.

Positionen des Schalters im Einschubrahmen

4. Inbetriebnahme; Putting into service

Einschalten; Closing the circuit-breaker

Einschalten

Procedures for switching the circuit-breaker ON, both mechanically and electrically.

Ausschalten; Switching off

Ausschalten

Procedures for switching the circuit-breaker OFF, via mechanical, electrical, or remote activation.

Inbetriebnahme nach Überstromauslöser-Auslösung

6. Inspektion; Inspection

7. Störungsbeseitigung (Troubleshooting)

Probleme beim Einschalten

Faults preventing the breaker from closing and their causes/remedies.

Probleme beim Verfahren

7. Troubleshooting (English)

Probleme beim Schließen

Breaker cannot be closed mechanically or electrically.

Probleme beim Verfahren

Breaker cannot be moved or cranked correctly.

Probleme mit der Schaltschranktür

Probleme mit der Schaltschranktür

Cubicle door cannot be opened or guide rails pulled out.