Terminals
Jumper positions: Jumper positions:
load-independent current load-independent voltage
To change the jumper positions, the following instructions must
be observed:
• Short circuit the ct’s if required.
• To remove lid from case insert a flat screwdriver approx.
0.8 * 3.5 mm with an angle of 45° into one after another of the
locking hooks and twist the screwdriver by approx. 45°.
Make a note of the location if necessary.
• Pull the modules half-way out by slightly moving them back and
forth.
• Change the jumper positions as required.
• Plug the modules back into the device
(position the power supply in the middle slot).
• Snap the cover back into its correct position.
Output 3